[65]
Comparator 5
See par. group LC-1#. If Comparator 5 is evaluated as TRUE, the output will go high. Otherwise, it
will be low.
[70]
Logic rule 0
See par. group LC-4#. If Logic Rule 0 is evaluated as TRUE, the output will go high. Otherwise, it
will be low.
[71]
Logic rule 1
See par. group LC-4#. If Logic Rule 1 is evaluated as TRUE, the output will go high. Otherwise, it
will be low.
[72]
Logic rule 2
See par. group LC-4#. If Logic Rule 2 is evaluated as TRUE, the output will go high. Otherwise, it
will be low.
[73]
Logic rule 3
See par. group LC-4#. If Logic Rule 3 is evaluated as TRUE, the output will go high. Otherwise, it
will be low.
[74]
Logic rule 4
See par. group LC-4#. If Logic Rule 4 is evaluated as TRUE, the output will go high. Otherwise, it
will be low.
[75]
Logic rule 5
See par. group LC-4#. If Logic Rule 5 is evaluated as TRUE, the output will go high. Otherwise, it
will be low.
[80]
SL digital output A
See par. 13-52
SL Controller Action
. The output will go high whenever the Logic Action [38]
Set dig.
out. A high
is executed. The output will go low whenever the Logic Action [32] Set dig. out. A low
is executed.
[81]
SL digital output B
See par. 13-52
SL Controller Action
. The input will go high whenever the Logic Action [39]
Set dig.
out. A high
is executed. The input will go low whenever the Logic Action [33]
Set dig. out. A low
is
executed.
[82]
SL digital output C
See par. 13-52
SL Controller Action
. The input will go high whenever the Logic Action [40]
Set dig.
out. A high
is executed. The input will go low whenever the Logic Action [34]
Set dig. out. A low
is
executed.
[83]
SL digital output D
See par. 13-52
SL Controller Action
. The input will go high whenever the Logic Action [41]
Set dig.
out. A
high is executed. The input will go low whenever the Logic Action [35]
Set dig. out. A low
is
executed.
[84]
SL digital output E
See par. 13-52
SL Controller Action
. The input will go high whenever the Logic Action [42]
Set dig.
out. A high
is executed. The input will go low whenever the Logic Action [36]
Set dig. out. A low
is
executed.
[85]
SL digital output F
See par. 13-52
SL Controller Action
. The input will go high whenever the Logic Action [43]
Set dig.
out. A high
is executed. The input will go low whenever the Logic Action [37]
Set dig. out. A low
is
executed.
[160]
No alarm
Output is high when no alarm is present.
[161]
Running reverse
Output is high when the frequency converter is running counter clockwise (the logical product of
the status bits ‘running’ AND ‘reverse’).
[165]
Local ref active
Output is high when par. 3-13
Reference Site
= [2] Local or when par. 3-13
Reference Site
= [0]
Linked to hand auto
at the same time as the LCP is in Hand mode.
[166]
Remote ref active
Output is high when par. 3-13
Reference Site
= Remote
[1] or
Linked to hand/auto
[0] while the
LCP is in [Auto] mode.
[167]
Start command act.
Output is high when there is an active Start command (i.e. via digital input bus connection or [Hand]
or [Auto]), and no Stop or Start command is active.
[168]
Hand mode
Output is high when the frequency converter is in Hand mode (as indicated by the LED light above
[Hand]).
2 Parameter Description
VLT
p
Automation VT Drive FC322
Programming Guide
88
MG.20.W1.22 - VLT
p
is a registered Danfoss trademark
2