0-04 Operating State at Power-up
Option:
Function:
Select the operating mode upon reconnection of the frequency converter to mains voltage after
power down when operating in Hand (local)mode.
[0] *
Resume
Resumes operation of the frequency converter maintaining the same local reference and the same
start/stop condition (applied by [Hand On]/[Off] on the LCP or Hand Start via a digital input as
before the frequency converter was powered down.
[1]
Forced stop, ref=old
Uses saved reference [1] to stop the frequency converter but at the same time retain in memory
the local speed reference prior to power down. After mains voltage is reconnected and after re-
ceiving a start command (using the LCP [Hand On] button or Hand Start command via a digital
input) the frequency converter restarts and operates at the retained speed reference.