23-61 Continuous Bin Data
Range:
Function:
0*
[0 - 4294967295 ]
Array with 10 elements ([0]-[9] below parameter number in display). Press OK and step between
elements by means of
Ⴃ
and
Ⴍ
buttons on the LCP.
10 counters with the frequency of occurrence for the operating variable monitored, sorted according
to the following intervals:
Counter [0]: 0% - <10%
Counter [1]: 10% - <20%
Counter [2]. 20% - <30%
Counter [3]: 30% - <40%
Counter [4]: 40% - <50%
Counter [5]: 50% - <60%
Counter [6]. 60% - <70%
Counter [7]: 70% - <80%
Counter [8]. 80% - <90%
Counter [9]: 90% - <100% or Max
The above minimum limits for the intervals are the default limits. These can be changed in
par. 23-65
Minimum Bin Value
.
Starts to count when the frequency converter is powered up for the first time. All counters can be
reset to 0 in par. 23-66
Reset Continuous Bin Data
.
23-62 Timed Bin Data
Range:
Function:
0*
[0 - 4294967295 ]
Array with 10 elements ([0]-[9] below parameter number in display). Press OK and step between
elements by means of
Ⴃ
and
Ⴍ
buttons on the LCP.
10 counters with the frequency of occurrence for the operating data monitored sorted according to
the intervals as for par. 23-61
Continuous Bin Data
.
Starts to count at the date/time programmed in par. 23-63
Timed Period Start
, and stops at the
time/date programmed in par. 23-64
Timed Period Stop
. All counters can be reset to 0 in
par. 23-67
Reset Timed Bin Data
.
23-63 Timed Period Start
Range:
Function:
Application
dependent*
[Application dependant]
NB!
The frequency converter has no back up of the clock function and the set date/time will reset to default (2000-01-01 00:00) after a
power down unless a Real Time Clock module with back up is installed. Consequently the logging will be stopped until date/time is
readjusted in par. 0-70
Date and Time
. In par. 0-79
Clock Fault
it is possible to program for a Warning in case clock not has been set
properly, e.g. after a power down.
NB!
When mounting an Analog I/O MCB109 option card, a battery back up of the date and time is included.
VLT
p
Automation VT Drive FC322
Programming Guide
2 Parameter Description
MG.20.W1.22 - VLT
p
is a registered Danfoss trademark
237