6-01 Live Zero Timeout Function
Option:
Function:
Select the time-out function. The function set in par. 6-01
Live Zero Timeout Function
will be acti-
vated if the input signal on terminal 53 or 54 is below 50% of the value in par. 6-10
Terminal 53
Low Voltage
, par. 6-12
Terminal 53 Low Current
, par. 6-20
Terminal 54 Low Voltage
or
par. 6-22
Terminal 54 Low Current
for a time period defined in par. 6-00
Live Zero Timeout Time
.
If several time-outs occur simultaneously, the frequency converter prioritises the time-out functions
as follows:
1.
par. 6-01
Live Zero Timeout Function
2.
par. 8-04
Control Timeout Function
The output frequency of the frequency converter can be:
•
[1] frozen at the present value
•
[2] overruled to stop
•
[3] overruled to jog speed
•
[4] overruled to max. speed
•
[5] overruled to stop with subsequent trip
[0] *
Off
[1]
Freeze output
[2]
Stop
[3]
Jogging
[4]
Max. speed
[5]
Stop and trip
2 Parameter Description
VLT
p
Automation VT Drive FC322
Programming Guide
100
MG.20.W1.22 - VLT
p
is a registered Danfoss trademark