2.13.9 No Trip at Inverter Overload
In some pump systems, the frequency converter has not been sized properly to yield the current needed in all points of the operational flow-head
characteristic. At these points, the pump will need a current higher than the rated current of the frequency converter. The frequency converter can yield
110% of the rated current continuously for 60 sec. If still overloaded, the frequency converter will normally trip (causing the pump to stop by coasting)
and provide an alarm.
It may be preferable to run the pump at reduced speed for a while in case it is not possible to run continuously with demanded capacity.
Select
Function at Inverter Overload
, par. 14-61
Function at Inverter Overload
to automatically reduce pump speed until the output current is below
100% of the rated current (set in par. 14-62
Inv. Overload Derate Current
).
The
Function at Inverter Overload
is an alternative to letting the frequency converter trip.
The frequency converter estimates the load on the power section by means of an inverter load counter, which will cause a warning at 98% and a reset
of the warning at 90%. At the value 100%, the frequency converter trips and provides an alarm.
Status for the counter can be read in par. 16-35
Inverter Thermal
.
If par. 14-61
Function at Inverter Overload
is set to Derate, the pump speed will be reduced when the counter exceeds 98, and stay reduced until the
counter has dropped below 90.7.
If par. 14-62
Inv. Overload Derate Current
is set e.g. to 95% a steady overload will cause the pump speed to fluctuate between values corresponding to
110% and 95% of rated output current for the frequency converter.
14-61 Function at Inverter Overload
Option:
Function:
[0]
Trip
[1] *
Derate
Is used in case of steady overload beyond the thermal limits (110% for 60 sec.).
Choose
Trip
[0] to make the frequency converter trip and provide an alarm or
Derate
[1] to reduce
pump speed in order to decrease the load on the power section and allowing this to cool down.
14-62 Inv. Overload Derate Current
Range:
Function:
95 %*
[50 - 100 %]
Defines the desired current level (in % of rated output current for the frequency converter) when
running with reduced pump speed after load on the frequency converter has exceeded the allowable
limit (110% for 60 sec.).