6-16 Terminal 53 Filter Time Constant
Range:
Function:
0.001 s*
[0.001 - 10.000 s]
Enter the time constant. This is a first-order digital low pass filter time constant for suppressing
electrical noise in terminal 53. A high time constant value improves dampening but also increases
the time delay through the filter.
This parameter cannot be adjusted while the motor is running.
6-17 Terminal 53 Live Zero
Option:
Function:
This parameter makes it possible to disable the Live Zero monitoring. E.g. to be used if the analog
outputs are used as part of a decentral I/O system (e.g. when not part of any frequency converter
related control functions, but feeding an external control system with data)
[0]
Disabled
[1] *
Enabled
2.8.4 6-2* Analog Input 2
Parameters for configuring the scaling and limits for analog input 2 (terminal 54).
6-20 Terminal 54 Low Voltage
Range:
Function:
0.07 V*
[Application dependant]
Enter the low voltage value. This analog input scaling value should correspond to the low reference/
feedback value, set in par. 6-24
Terminal 54 Low Ref./Feedb. Value
.
6-21 Terminal 54 High Voltage
Range:
Function:
10.00 V*
[Application dependant]
Enter the high voltage value. This analog input scaling value should correspond to the high refer-
ence/feedback value set in par. 6-25
Terminal 54 High Ref./Feedb. Value
.
6-22 Terminal 54 Low Current
Range:
Function:
4.00 mA*
[Application dependant]
Enter the low current value. This reference signal should correspond to the low reference/feedback
value, set in par. 6-24
Terminal 54 Low Ref./Feedb. Value
. The value must be set at >2 mA in order
to activate the Live Zero Time-out Function in par. 6-01
Live Zero Timeout Function
.
6-23 Terminal 54 High Current
Range:
Function:
20.00 mA* [Application dependant]
Enter the high current value corresponding to the high reference/feedback value set in
par. 6-25
Terminal 54 High Ref./Feedb. Value
.
6-24 Terminal 54 Low Ref./Feedb. Value
Range:
Function:
0.000*
[-999999.999 - 999999.999 ]
Enter the analog input scaling value that corresponds to the low voltage/low current value set in
par. 6-20
Terminal 54 Low Voltage
and par. 6-22
Terminal 54 Low Current
.
2 Parameter Description
VLT
p
Automation VT Drive FC322
Programming Guide
102
MG.20.W1.22 - VLT
p
is a registered Danfoss trademark
2