Illustration 2.3: Controlled Ramp-down, longer mains failure. Ramping down as long as the energy in the system allows for it, then the motor
is coasted.
Illustration 2.4: Kinetic Back-up, short mains failure. Ride through as long as the energy in the system allows for it.
Illustration 2.5: Kinetic Back-up, longer mains failure. The motor is coasted as soon as the energy in the system is too low.
14-11 Mains Voltage at Mains Fault
Range:
Function:
Application
dependent*
[180 - 600 V]
This parameter defines the threshold voltage at which the selected function in par. 14-10
Mains
Failure
should be activated.
14-12 Function at Mains Imbalance
Option:
Function:
Operation under severe main imbalance conditions reduces the lifetime of the motor. Conditions are
considered severe if the motor is operated continuously near nominal load (e.g. a pump or fan
running near full speed).
When a severe mains imbalance is detected:
[0] *
Trip
Select
Trip
[0] to trip the frequency converter.
[1]
Warning
Select
Warning
[1] to issue a warning.
[2]
Disabled
Select
Disabled
[2] for no action.
[3] *
Derate
Select
Derate
[3] for derating the frequency converter.
2.13.4 14-2* Trip Reset
Parameters for configuring auto reset handling, special trip handling and control card self test or initialisation.