NB!
An active HAND-OFF-AUTO signal via the digital inputs has higher priority than the control keys [Hand on] [Auto on].
[Reset]
is used for resetting the frequency converter after an alarm (trip). The key can be
Enabled
[1] or
Disabled
[0] via par. 0-43
[Reset] Key on LCP
.
1.1.6 Parameter Set-Up
The frequency converter can be used for practically all assignments, thus offering a significant number of parameters. The series offers a choice between
two programming modes - a Quick Menu mode and a Main Menu mode.
The latter provides access to all parameters. The former takes the user through a few parameters making it possible to
program the majority of
water/ wastewater applications
.
Regardless of the mode of programming, you can change a parameter both in the Quick Menu mode and in the Main Menu mode.
1.1.7 Quick Menu Mode
The GLCP provides access to all parameters listed under the Quick Menus. To set parameters using the [Quick Menu] button:
Pressing [Quick Menu] the list indicates the different areas contained in the Quick menu.
Efficient Parameter Set-up for Water Applications
The parameters can easily be set up for the vast majority of the water and wastewater applications only by using the
[Quick Menu]
.
The optimum way to set parameters through the [Quick Menu] is by following the below steps:
1.
Press [Quick Setup] for selecting basic motor settings, ramp times, etc.
2.
Press [Function Setups] for setting up the required functionality of the frequency converter - if not already covered by the settings in [Quick
Setup].
3.
Choose between
General Settings
,
Open Loop Settings
and
Closed Loop Settings.
It is recommended to do the set-up in the order listed.
Illustration 1.6: Quick menu view.
Par.
Designation
[Units]
0-01
Language
1-20
Motor Power
[kW]
1-22
Motor Voltage
[V]
1-23
Motor Frequency
[Hz]
1-24
Motor Current
[A]
1-25
Motor Nominal Speed
[RPM]
3-41
Ramp 1 Ramp up Time
[s]
3-42
Ramp 1 Ramp down Time
[s]
4-11
Motor Speed Low Limit
[RPM]
4-13
Motor Speed High Limit
[RPM]
1-29
Automatic Motor Adaptation (AMA)
Table 1.1: Quick Setup parameters
If
No Operation
is selected in terminal 27 no connection to +24 V on terminal 27 is necessary to enable start.
If
Coast Inverse
(factory default value) is selected in Terminal 27, a connection to +24V is necessary to enable start.
1 How to Programme
VLT
p
Automation VT Drive FC322
Programming Guide
14
MG.20.W1.22 - VLT
p
is a registered Danfoss trademark