[33]
Digital input DI18
Use the value of DI18 in the logic rule (High = TRUE).
[34]
Digital input DI19
Use the value of DI19 in the logic rule (High = TRUE).
[35]
Digital input DI27
Use the value of DI27 in the logic rule (High = TRUE).
[36]
Digital input DI29
Use the value of DI29 in the logic rule (High = TRUE).
[37]
Digital input DI32
Use the value of DI32 in the logic rule (High = TRUE).
[38]
Digital input DI33
Use the value of DI33 in the logic rule (High = TRUE).
[39]
Start command
This logic rule is TRUE if the frequency converter is started by any means (either via digital input,
field bus or other).
[40]
Drive stopped
This logic rule is TRUE if the frequency converter is stopped or coasted by any means (either via
digital input, fieldbus or other).
[41]
Reset Trip
This logic rule is TRUE if the frequency converter is tripped (but not trip-locked) and the reset button
is pressed.
[42]
Auto Reset Trip
This logic rule is TRUE if the frequency converter is tripped (but not trip-locked) and an Automatic
Reset is issued.
[43]
OK Key
This logic rule is TRUE if the OK key on the LCP is pressed.
[44]
Reset Key
This logic rule is TRUE if the Reset key on the LCP is pressed.
[45]
Left Key
This logic rule is TRUE if the Left key on the LCP is pressed.
[46]
Right Key
This logic rule is TRUE if the Right key on the LCP is pressed.
[47]
Up Key
This logic rule is TRUE if the Up key on the LCP is pressed.
[48]
Down Key
This logic rule is TRUE if the Down key on the LCP is pressed.
[50]
Comparator 4
Use the result of comparator 4 in the logic rule.
[51]
Comparator 5
Use the result of comparator 5 in the logic rule.
[60]
Logic rule 4
Use the result of logic rule 4 in the logic rule.
[61]
Logic rule 5
Use the result of logic rule 5 in the logic rule.
[70]
SL Time-out 3
Use the result of timer 3 in the logic rule.
[71]
SL Time-out 4
Use the result of timer 4 in the logic rule.
[72]
SL Time-out 5
Use the result of timer 5 in the logic rule.
[73]
SL Time-out 6
Use the result of timer 6 in the logic rule.
[74]
SL Time-out 7
Use the result of timer 7 in the logic rule.
[80]
No Flow
[81]
Dry Pump
[82]
End of Curve
[83]
Broken Belt
2 Parameter Description
VLT
p
Automation VT Drive FC322
Programming Guide
148
MG.20.W1.22 - VLT