2.19 Main Menu - Time-based Functions - Group 23
2.20.1 23-0* Timed Actions
Use
Timed Actions
for actions needing to be performed on a daily or weekly basis, e.g. different references for working hours / non-working hours. Up
to 10 Timed Actions can be programmed in the frequency converter. The Timed Action number is selected from the list when entering parameter group
23-0* from the LCP. par. 23-00
ON Time
– par. 23-04
Occurrence
then refer to the selected Timed Action number. Each Timed Action is divided into an
ON time and an OFF time, in which two different actions may be performed.
NB!
The clock (parameter group 0-7*) must be correctly programmed for Timed Actions to function correctly.
NB!
When mounting an Analog I/O MCB109 option card, a battery back up of the date and time is included.
23-00 ON Time
Array [10]
Range:
Function:
Application
dependent*
[Application dependant]
23-01 ON Action
Arra [10]
Option:
Function:
Select the action during ON Time. See par. 13-52
SL Controller Action
for descriptions of the options.
[0] *
Disabled
[1]
No action
[2]
Select set-up 1
[3]
Select set-up 2
[4]
Select set-up 3
[5]
Select set-up 4
[10]
Select preset ref 0
[11]
Select preset ref 1
[12]
Select preset ref 2
[13]
Select preset ref 3
[14]
Select preset ref 4
[15]
Select preset ref 5
[16]
Select preset ref 6
[17]
Select preset ref 7
[18]
Select ramp 1
[19]
Select ramp 2
2 Parameter Description
VLT
p
Automation VT Drive FC322
Programming Guide
226
MG.20.W1.22 - VLT