[137]
Speed 4-20mA
: 0 - Speed High Limit (par. 4-13 and par. 4-14)
[138]
Torque 4-20mA
:
[139]
Bus ctrl.
: 0 - 100%, (0-20 mA)
[140]
Bus ctrl. 4-20 mA
: 0 - 100%
[141]
Bus ctrl t.o.
: 0 - 100%, (0-20 mA)
[142]
Bus ctrl t.o. 4-20mA
: 0 - 100%
[143]
Ext. CL 1 4-20mA
: 0 - 100%
[144]
Ext. CL 2 4-20mA
: 0 - 100%
[145]
Ext. CL 3 4-20mA
: 0 - 100%
[146]
Cascade Ref. 4-20mA
:
[150]
Out frq 0-Fmax 4-20mA
:
NB!
Values for setting the Minimum Reference is found in open loop par. 3-02
Minimum Reference
and for closed loop par. 20-13
Minimum Reference/
Feedb.
- values for maximum reference for open loop is found in par. 3-03
Maximum Reference
and for closed loop par. 20-14
Maximum Reference/
Feedb.
.
6-51 Terminal 42 Output Min Scale
Range:
Function:
0.00 %*
[0.00 - 200.00 %]
Scale for the minimum output (0 or 4 mA) of the analogue signal at terminal 42.
Set the value to be the
percentage
of the full range of the variable selected in par. 6-50
Terminal
42 Output
.
6-52 Terminal 42 Output Max Scale
Range:
Function:
100.00 %* [0.00 - 200.00 %]
Scale for the maximum output (20 mA) of the analog signal at terminal 42.
Set the value to be the percentage of the full range of the variable selected in par. 6-50
Terminal
42 Output
.
It is possible to get a value lower than 20 mA at full scale by programming values >100% by using
a formula as follows:
20
mA
/
desired
maximum
current
× 100 %
i
.
e
. 10
mA
:
20
mA
10
mA
× 100 % = 200 %
2 Parameter Description
VLT
p
Automation VT Drive FC322
Programming Guide
106