4-53 Warning Speed High
Range:
Function:
Application
dependent*
[Application dependant]
NB!
Any changes in par. 4-13
Motor Speed High Limit [RPM]
will reset the value in par. 4-53
Warning Speed High
to the same value as set
in par. 4-13
Motor Speed High Limit [RPM]
.
If a different value is needed in par. 4-53
Warning Speed High
, it must be set after programming of par. 4-13
Motor Speed High Limit
[RPM]
!
4-54 Warning Reference Low
Range:
Function:
-999999.99
9*
[Application dependant]
Enter the lower reference limit. When the actual reference falls below this limit, the display indicates
Ref Low. The signal outputs can be programmed to produce a status signal on terminal 27 or 29
and on relay output 01 or 02.
4-55 Warning Reference High
Range:
Function:
999999.999
*
[Application dependant]
Enter the upper reference limit. When the actual reference exceeds this limit, the display reads Ref
High. The signal outputs can be programmed to produce a status signal on terminal 27 or 29 and
on relay output 01 or 02.
4-56 Warning Feedback Low
Range:
Function:
-999999.99
9 Referen-
ceFeedback-
Unit*
[Application dependant]
Enter the lower feedback limit. When the feedback falls below this limit, the display reads Feedb
Low. The signal outputs can be programmed to produce a status signal on terminal 27 or 29 and
on relay output 01 or 02.
4-57 Warning Feedback High
Range:
Function:
999999.999
Reference-
FeedbackU-
nit*
[Application dependant]
Enter the upper feedback limit. When the feedback exceeds this limit, the display reads Feedb High.
The signal outputs can be programmed to produce a status signal on terminal 27 or 29 and on relay
output 01 or 02.
4-58 Missing Motor Phase Function
Option:
Function:
Displays an alarm in the event of a missing motor phase.
Select 100 ms to have a short detection time and alarm in the event of a missing motor phase. 100
ms is recommended for hoisting applications.
[0]
Disabled
No alarm is displayed if a missing motor phase occurs.
[1] *
Trip 100 ms
An alarm is displayed if a missing motor phase occurs.
[2] *
Trip 1000 ms
2 Parameter Description
VLT
p
Automation VT Drive FC322
Programming Guide
68