[54]
Auto start
A signal applied will put the frequency converter into Auto mode as if the LCP button
Auto On
has
been pressed. See also
Hand Start
[53]
[55]
DigiPot Increase
Uses the input as an INCREASE signal to the Digital Potentiometer function described in parameter
group 3-9*
[56]
DigiPot Decrease
Uses the input as a DECREASE signal to the Digital Potentiometer function described in parameter
group 3-9*
[57]
DigiPot Clear
Uses the input to CLEAR the Digital Potentiometer reference described in parameter group 3-9*
[60]
Counter A (up)
(Terminal 29 or 33 only) Input for increment counting in the SLC counter.
[61]
Counter A (down)
(Terminal 29 or 33 only) Input for decrement counting in the SLC counter.
[62]
Reset Counter A
Input for reset of counter A.
[63]
Counter B (up)
(Terminal 29 and 33 only) Input for increment counting in the SLC counter.
[64]
Counter B (down)
(Terminal 29 and 33 only) Input for decrement counting in the SLC counter.
[65]
Reset Counter B
Input for reset of counter B.
[66]
Sleep Mode
Forces frequency converter into Sleep Mode (see par. 22-4*, Sleep Mode). Reacts on the rising edge
of signal applied!
[78]
Reset Preventive Maintenance Word Resets all data in par. 16-96, Preventive Maintenance Word, to 0.
The below setting options are all related to the Cascade Controller. Wiring diagrams and settings for parameter, see group 25-** for more details.
[120]
Lead Pump Start
Starts/Stops the Lead Pump (controlled by the frequency converter). A start requires that also a
System Start signal has been applied e.g. to one of the digital inputs set for
Start
[8]!
[121]
Lead Pump Alternation
Forces alternation of the lead pump in a Cascade Controller.
Lead Pump Alternation
, par. 25-50,
must be set to either
At Command
[2] or
At Staging or At Command
[3].
Alternation Event
, par.
25-51, can be set to any of the four options.
[130 - 138] Pump1 Interlock - Pump9 Interlock
The function will depend on the setting in par. 25-06, Number of Pumps. If set to
No
[0], then
Pump1 refers to the pump controlled by relay RELAY1 etc. If set to
Yes
[1], Pump1 refers to the
pump controlled by the frequency converter only (without any of the build in relays involved) and
Pump2 to the pump controlled by the relay RELAY1. Variable speed pump (lead) cannot be inter-
locked in the basic Cascade Controller.
See below table:
Setting in Par. 5-1*
Setting in Par. 25-06
[0] No
[1] Yes
[130] Pump1 Interlock
Controlled by RELAY1
(only if not lead pump)
Frequency Converter control-
led
(cannot be interlocked)
[131] Pump2 Interlock
Controlled by RELAY2
Controlled by RELAY1
[132] Pump3 Interlock
Controlled by RELAY3
Controlled by RELAY2
[133] Pump4 Interlock
Controlled by RELAY4
Controlled by RELAY3
[134] Pump5 Interlock
Controlled by RELAY5
Controlled by RELAY4
[135] Pump6 Interlock
Controlled by RELAY6
Controlled by RELAY5
[136] Pump7 Interlock
Controlled by RELAY7
Controlled by RELAY6
[137] Pump8 Interlock
Controlled by RELAY8
Controlled by RELAY7
[138] Pump9 Interlock
Controlled by RELAY9
Controlled by RELAY8
5-10 Terminal 18 Digital Input
Option:
Function:
[0]
No operation
[1]
Reset
2 Parameter Description
VLT
p
Automation VT Drive FC322
Programming Guide
76
MG.20.W1.22 - VLT
p
is a registered Danfoss trademark