[1] *
Enabled
26-20 Terminal X42/3 Low Voltage
Range:
Function:
0.07 V*
[Application dependant]
Enter the low voltage value. This analog input scaling value should correspond to the low reference/
feedback value set in par. 26-24
Term. X42/3 Low Ref./Feedb. Value
.
26-21 Terminal X42/3 High Voltage
Range:
Function:
10.00 V*
[Application dependant]
Enter the high voltage value. This analog input scaling value should correspond to the high refer-
ence/feedback value set in par. 26-25
Term. X42/3 High Ref./Feedb. Value
.
26-24 Term. X42/3 Low Ref./Feedb. Value
Range:
Function:
0.000*
[-999999.999 - 999999.999 ]
Enter the analog input scaling value that corresponds to the low voltage value set in
par. 26-20
Terminal X42/3 Low Voltage
.
26-25 Term. X42/3 High Ref./Feedb. Value
Range:
Function:
100.000*
[-999999.999 - 999999.999 ]
Enter the analog input scaling value that corresponds to the high voltage value set in
par. 26-21
Terminal X42/3 High Voltage
.
26-26 Term. X42/3 Filter Time Constant
Range:
Function:
0.001 s*
[0.001 - 10.000 s]
Enter the time constant. This is a first-order digital low pass filter time constant for suppressing
noise in terminal X42/3. A high time constant value improves dampening but also increases the time
delay through the filter. This parameter cannot be adjusted while the motor is running.
26-27 Term. X42/3 Live Zero
Option:
Function:
This parameter makes it possible to enable the Live Zero monitoring. E.g. where the analog input
is a part of the frequency converter control, rather than being used as part of a decentral I/O system,
such as a Building Management System.
[0]
Disabled
[1] *
Enabled
26-30 Terminal X42/5 Low Voltage
Range:
Function:
0.07 V*
[Application dependant]
Enter the low voltage value. This analog input scaling value should correspond to the low reference/
feedback value set in par. 26-34
Term. X42/5 Low Ref./Feedb. Value
.
26-31 Terminal X42/5 High Voltage
Range:
Function:
10.00 V*
[Application dependant]
Enter the high voltage value. This analog input scaling value should correspond to the high refer-
ence/feedback value set in par. 26-35
Term. X42/5 High Ref./Feedb. Value
.