[137]
Pump 8 Interlock
[138]
Pump 9 Interlock
5-11 Terminal 19 Digital Input
Option:
Function:
[0] *
No operation
Same options and functions as 5-1*, except for
Pulse input
.
Option:
Function:
5-12 Terminal 27 Digital Input
Option:
Function:
Same options and functions as par. 5-1*, except for
Pulse input
.
[0] *
No operation
5-13 Terminal 29 Digital Input
Option:
Function:
Same options and functions as par. 5-1*.
[14] *
Jog
5-14 Terminal 32 Digital Input
Option:
Function:
[0] *
No operation
Same options and functions as par. 5-1*, except for
Pulse input
.
[1]
Reset
[2]
Coast inverse
[3]
Coast and reset inv
[5]
DC-brake inverse
[6]
Stop inverse
[7]
External interlock
[8]
Start
[9]
Latched start
[10]
Reversing
[11]
Start reversing
[14]
Jog
[15]
Preset reference on
[16]
Preset ref bit 0
[17]
Preset ref bit 1
[18]
Preset ref bit 2
[19]
Freeze reference
[20]
Freeze output
[21]
Speed up
[22]
Speed down
[23]
Set-up select bit 0
[24]
Set-up select bit 1
[34]
Ramp bit 0
[36]
Mains failure inverse
[51]
Hand/Auto Start
2 Parameter Description
VLT
p
Automation VT Drive FC322
Programming Guide
78
MG.20.W1.22 - VLT
p
is a registered Danfoss trademark
2