NB!
If the set-point is reached after staging before the variable speed pump reaches its minimum speed - the system will enter the state closed loop as
soon as the feedback pressure is crossing the set-point.
25-43 Destaging Threshold
Range:
Function:
Application
dependent*
[Application dependant]
NB!
If the set-point is reached after staging before the variable speed pump reaches its maximum speed - the system will enter the state closed loop as
soon as the feedback pressure is crossing the set-point.
25-44 Staging Speed [RPM]
Range:
Function:
0 RPM*
[0 - 0 RPM]
Readout of the below calculated value for Staging Speed When adding a fixed speed pump, in order
to prevent an overshoot of pressure, the variable speed pump ramps down to a lower speed. When
the variable speed pump reaches the “Staging Speed” the fixed speed pump is staged on. Staging
Speed calculation is based on par. 25-42
Staging Threshold
, and par. 4-13
Motor Speed High Limit
[RPM]
.
Staging Speed is calculated with the following formula:
STAGE
=
HIGH
STAGE
%
100
where n
HIGH
is Motor Speed High Limit and n
STAGE100%
is the value of Staging Threshold.
VLT
p
Automation VT Drive FC322
Programming Guide
2 Parameter Description
MG.20.W1.22 - VLT
p
is a registered Danfoss trademark
247