9-53 Profibus Warning Word
Range:
Function:
0*
[0 - 65535 ]
This parameter displays Profibus communication warnings. Please refer to the
Profibus Operating
Instructions
for further information.
Read only
Bit:
Meaning:
0
Connection with DP-master is not ok
1
Not used
2
FDLNDL (Fieldbus Data link Layer) is not ok
3
Clear data command received
4
Actual value is not updated
5
Baudrate search
6
PROFIBUS ASIC is not transmitting
7
Initializing of PROFIBUS is not ok
8
Frequency converter is tripped
9
Internal CAN error
10
Wrong configuration data from PLC
11
Wrong ID sent by PLC
12
Internal error occured
13
Not configured
14
Timeout active
15
Warning 34 active
9-63 Actual Baud Rate
Option:
Function:
This parameter displays the actual Profibus baud rate. The Profibus Master automatically sets the
baud rate.
[0]
9,6 kbit/s
[1]
19,2 kbit/s
[2]
93,75 kbit/s
[3]
187,5 kbit/s
[4]
500 kbit/s
[6]
1500 kbit/s
[7]
3000 kbit/s
[8]
6000 kbit/s
[9]
12000 kbit/s
[10]
31,25 kbit/s
[11]
45,45 kbit/s
[255] *
No baudrate found
9-65 Profile Number
Range:
Function:
0*
[0 - 0 ]
This parameter contains the profile identification. Byte 1 contains the profile number and byte 2 the
version number of the profile.
VLT
p
Automation VT Drive FC322
Programming Guide
2 Parameter Description
MG.20.W1.22 - VLT
p
is a registered Danfoss trademark
127
2