2.15.6 16-6* Inputs and Outputs
Parameters for reporting the digital and analog IO ports.
16-60 Digital Input
Range:
Function:
0*
[0 - 63]
View the signal states from the active digital inputs. Input 18 corresponds for example to bit 5. '0'
= NO signal, '1' = connected signal.
Bit 0
Digital input term. 33
Bit 1
Digital input term. 32
Bit 2
Digital input term. 29
Bit 3
Digital input term. 27
Bit 4
Digital input term. 19
Bit 5
Digital input term. 18
Bit 6
Digital input term. 37
Bit 7
Digital input GP I/O term. X30/2
Bit 8
Digital input GP I/O term. X30/3
Bit 9
Digital input GP I/O term. X30/4
Bit 10-63
Reserved for future terminals
16-61 Terminal 53 Switch Setting
Option:
Function:
View the setting of input terminal 53. Current = 0; Voltage = 1.
[0] *
Current
[1]
Voltage
[2]
Pt 1000 [°C]
[3]
Pt 1000 [°F]
[4]
Ni 1000 [°C]
[5]
Ni 1000 [°F]
16-62 Analog Input 53
Range:
Function:
0.000*
[-20.000 - 20.000 ]
View the actual value at input 53.
16-63 Terminal 54 Switch Setting
Option:
Function:
View the setting of input terminal 54. Current = 0; Voltage = 1.
[0] *
Current
[1]
Voltage
[2]
Pt 1000 [°C]
[3]
Pt 1000 [°F]
[4]
Ni 1000 [°C]
[5]
Ni 1000 [°F]
VLT
p
Automation VT Drive FC322
Programming Guide
2 Parameter Description
MG.20.W1.22 - VLT
p
is a registered Danfoss trademark