6-02 Fire Mode Live Zero Timeout Function
Option:
Function:
The function set in par. 6-01
Live Zero Timeout Function
will be activated if the input signal on
analogue inputs is below 50% of the value defined in parameter group 6-1* to 6-6* "Terminal xx
Low Current” or “Terminal xx Low Voltage" for a time period defined in par. 6-00
Live Zero Timeout
Time
.
[0] *
Off
[1]
Freeze output
[2]
Stop
[3]
Jogging
[4]
Max. speed
2.8.3 6-1* Analog Input 1
Parameters for configuring the scaling and limits for analog input 1 (terminal 53).
6-10 Terminal 53 Low Voltage
Range:
Function:
0.07 V*
[Application dependant]
Enter the low voltage value. This analog input scaling value should correspond to the low reference/
feedback value set in par. 6-14
Terminal 53 Low Ref./Feedb. Value
.
6-11 Terminal 53 High Voltage
Range:
Function:
10.00 V*
[Application dependant]
Enter the high voltage value. This analog input scaling value should correspond to the high refer-
ence/feedback value set in par. 6-15
Terminal 53 High Ref./Feedb. Value
.
6-12 Terminal 53 Low Current
Range:
Function:
4.00 mA*
[Application dependant]
Enter the low current value. This reference signal should correspond to the low reference/feedback
value, set in par. 6-14
Terminal 53 Low Ref./Feedb. Value
. The value must be set at >2 mA in order
to activate the Live Zero Time-out Function in par. 6-01
Live Zero Timeout Function
.
6-13 Terminal 53 High Current
Range:
Function:
20.00 mA* [Application dependant]
Enter the high current value corresponding to the high reference/feedback set in par. 6-15
Terminal
53 High Ref./Feedb. Value
.
6-14 Terminal 53 Low Ref./Feedb. Value
Range:
Function:
0.000*
[-999999.999 - 999999.999 ]
Enter the analog input scaling value that corresponds to the low voltage/low current set in
par. 6-10
Terminal 53 Low Voltage
and par. 6-12
Terminal 53 Low Current
.
6-15 Terminal 53 High Ref./Feedb. Value
Range:
Function:
Application
dependent*
[-999999.999 - 999999.999 ]
Enter the analog input scaling value that corresponds to the high voltage/high current value set in
par. 6-11
Terminal 53 High Voltage
and par. 6-13
Terminal 53 High Current
.
VLT
p
Automation VT Drive FC322
Programming Guide
2 Parameter Description
MG.20.W1.22 - VLT
p
is a registered Danfoss trademark
101