1.1.16 Initialisation to Default Settings
Initialise the frequency converter to default settings in two ways:
Recommended initialisation (via par. 14-22
Operation Mode
)
1.
Select par. 14-22
Operation Mode
2.
Press [OK]
3.
Select “Initialisation”
4.
Press [OK]
5.
Cut off the mains supply and wait until the display turns off.
6.
Reconnect the mains supply - the frequency converter is now reset.
7.
Change par. 14-22
Operation Mode
back to
Normal Operation
.
NB!
Resets parameters selected in Personal Menu with default factory setting.
par. 14-22
Operation Mode
initialises all except:
par. 14-50
RFI Filter
par. 8-30
Protocol
par. 8-31
Address
par. 8-32
Baud Rate
par. 8-35
Minimum Response Delay
par. 8-36
Max Response Delay
par. 8-37
Maximum Inter-Char Delay
par. 15-00
Operating Hours
to par. 15-05
Over Volt's
par. 15-20
Historic Log: Event
to par. 15-22
Historic Log: Time
par. 15-30
Alarm Log: Error Code
to par. 15-32
Alarm Log: Time
Manual initialisation
1.
Disconnect from mains and wait until the display turns off.
2a.
Press [Status] - [Main Menu] - [OK] at the same time while power up for LCP 102, Graphical Display
2b.
Press [Menu] while power up for LCP 101, Numerical Display
3.
Release the keys after 5 s.
4.
The frequency converter is now programmed according to default settings.
This procedure initializes all except: par. 15-00
Operating Hours
; par. 15-03
Power Up's
; par. 15-04
Over Temp's
; par. 15-05
Over Volt's
.
NB!
When you carry out manual initialisation, you also reset serial communication, par. 14-50
RFI Filter
and fault log settings.
Removes parameters selected in par. 25-00
Cascade Controller
.
NB!
After initialization and power cycling, the display will not show any information until after a couple of minutes.
1 How to Programme
VLT
p
Automation VT Drive FC322
Programming Guide
20
MG.20.W1.22 - VLT
p
is a registered Danfoss trademark
1