8-30 Protocol
Option:
Function:
Protocol selection for the integrated FC (standard) Port (RS485) on the control card.
[0] *
FC
Communication according to the FC Protocol as described in
RS-485 Installation and Set-up
.
[1]
FC MC
Same as
FC
[0] but to be used when downloading SW to the frequency converter or uploading dll
file (covering information regarding parameters available in the frequency converter and their inter-
dependencies) to Motion Control Tool MCT10.
[2]
Modbus RTU
Communication according to the Modbus RTU protocol.
[9]
FC option
8-31 Address
Range:
Function:
Application
dependent*
[Application dependant]
8-32 Baud Rate
Option:
Function:
Baud rate selection depends on Protocol selection in par. 8-30
Protocol
.
[0]
2400 Baud
[1]
4800 Baud
[2] *
9600 Baud
[3]
19200 Baud
[4]
38400 Baud
[5]
57600 Baud
[6]
76800 Baud
[7]
115200 Baud
Default refers to the FC Protocol.
8-33 Parity / Stop Bits
Option:
Function:
Parity and Stop Bits for the protocol par. 8-30
Protocol
using the FC Port. For some of the protocols,
not all options will be visible. Default depends on the protocol selected.
[0] *
Even Parity, 1 Stop Bit
[1]
Odd Parity, 1 Stop Bit
[2]
No Parity, 1 Stop Bit
[3]
No Parity, 2 Stop Bits
8-35 Minimum Response Delay
Range:
Function:
Application
dependent*
[Application dependant]
8-36 Max Response Delay
Range:
Function:
Application
dependent*
[Application dependant]
2 Parameter Description
VLT
p
Automation VT Drive FC322
Programming Guide
114
MG.20.W1.22 - VLT
p
is a registered Danfoss trademark