2.3.5 1-6* Load Depend. Setting
Parameters for adjusting the load-dependent motor settings.
1-60 Low Speed Load Compensation
Range:
Function:
100 %*
[0 - 300 %]
Enter the % value to compensate voltage in relation to load when the motor is running at low speed
and obtain the optimum U/f characteristic. The motor size determines the frequency range within
which this parameter is active.
Motor size
Change over
0.25 kW - 7.5 kW
< 10 Hz
11 kW - 45 kW
< 5 Hz
55 kW - 550 kW
< 3-4 Hz
VLT
p
Automation VT Drive FC322
Programming Guide
2 Parameter Description
MG.20.W1.22 - VLT
p
is a registered Danfoss trademark
47
2