Illustration 2.6: Legend: FC=frequency converter; f
O
=frequency out; P
S
=P system; P
SL
=P setpoint
1) Systems where the integrated PI controller is used for controlling pressure or temperature e.g. boost systems with a pressure feed back signal applied
to the frequency converter from a pressure transducer. Par. 1-00,
Configuration Mode
, must be set for Closed Loop and the PI Controller configured for
desired reference and feed back signals.
Example: Boost system.
If no flow is detected, the frequency converter will increase the set point for pressure to ensure a slight over pressure in the system (boost to be set in
par. 22-45,
Setpoint Boost
).
The feedback from the pressure transducer is monitored and when this pressure has dropped with a set percentage below the normal set point for
pressure (Pset), the motor will ramp up again and pressure will be controlled for reaching the set value (Pset).
VLT
p
Automation VT Drive FC322
Programming Guide
2 Parameter Description
MG.20.W1.22 - VLT
p
is a registered Danfoss trademark
217
2
Remote Site Products - 1-888-532-2706 - www.remotesiteproducts.com
http://www.remotesiteproducts.com/p-20772-Danfoss-131X8135-VLT-Automation-VT-Drive-VFD-FC322-230V-5-HP.aspx