Priority of calculation
The results of par. 13-40
Logic Rule Boolean 1
, par. 13-41
Logic Rule Operator 1
and par. 13-42
Logic Rule Boolean 2
are calculated first. The outcome
(TRUE / FALSE) of this calculation is combined with the settings of par. 13-43
Logic Rule Operator 2
and par. 13-44
Logic Rule Boolean 3
, yielding the
final result (TRUE / FALSE) of the logic rule.