1.1.14 Changing of Data Value, Step-by-Step
Certain parameters can be changed step by step or infinitely variably. This applies to par. 1-20
Motor Power [kW]
, par. 1-22
Motor Voltage
and
par. 1-23
Motor Frequency
.
The parameters are changed both as a group of numeric data values and as numeric data values infinitely variably.
1.1.15 Read-out and Programming of Indexed Parameters
Parameters are indexed when placed in a rolling stack.
par. 15-30
Alarm Log: Error Code
to par. 15-32
Alarm Log: Time
contain a fault log which can be read out. Choose a parameter, press [OK], and use the
up/down navigation keys to scroll through the value log.
Use par. 3-10
Preset Reference
as another example:
Choose the parameter, press [OK], and use the up/down navigation keys keys to scroll through the indexed values. To change the parameter value,
select the indexed value and press [OK]. Change the value by using the up/down keys. Press [OK] to accept the new setting. Press [Cancel] to abort.
Press [Back] to leave the parameter.
VLT
p
Automation VT Drive FC322
Programming Guide
1 How to Programme
MG.20.W1.22 - VLT
p
is a registered Danfoss trademark