[12]
Select preset ref 2
Selects preset reference 2.
[13]
Select preset ref 3
Selects preset reference 3.
[14]
Select preset ref 4
Selects preset reference 4.
[15]
Select preset ref 5
Selects preset reference 5.
[16]
Select preset ref 6
Selects preset reference 6.
[17]
Select preset ref 7
Selects preset reference 7. If the active preset reference is changed, it will merge with other preset
reference commands coming from either the digital inputs or via a fieldbus.
[18]
Select ramp 1
Selects ramp 1
[19]
Select ramp 2
Selects ramp 2
[22]
Run
Issues a start command to the frequency converter.
[23]
Run reverse
Issues a start reverse command to the frequency converter.
[24]
Stop
Issues a stop command to the frequency converter.
[26]
DC Brake
Issues a DC stop command to the frequency converter.
[27]
Coast
The frequency converter coasts immediately. All stop commands including the coast command stop
the SLC.
[28]
Freeze output
Freezes the output frequency of the frequency converter.
[29]
Start timer 0
Starts timer 0, see par. 13-20
SL Controller Timer
for further description.
[30]
Start timer 1
Starts timer 1, see par. 13-20
SL Controller Timer
for further description.
[31]
Start timer 2
Starts timer 2, see par. 13-20
SL Controller Timer
for further description.
[32]
Set digital out A low
Any output with ‘digital output 1’ selected is low (off).
[33]
Set digital out B low
Any output with ‘digital output 2’ selected is low (off).
[34]
Set digital out C low
Any output with ‘digital output 3’ selected is low (off).
[35]
Set digital out D low
Any output with ‘digital output 4’ selected is low (off).
[36]
Set digital out E low
Any output with ‘digital output 5’ selected is low (off).
[37]
Set digital out F low
Any output with ‘digital output 6’ selected is low (off).
[38]
Set digital out A high
Any output with ‘digital output 1’ selected is high (closed).
[39]
Set digital out B high
Any output with ‘digital output 2’ selected is high (closed).
[40]
Set digital out C high
Any output with ‘digital output 3’ selected is high (closed).
[41]
Set digital out D high
Any output with ‘digital output 4’ selected is high (closed).
[42]
Set digital out E high
Any output with ‘digital output 5’ selected is high (closed).
[43]
Set digital out F high
Any output with ‘digital output 6’ selected is high (closed).
[60]
Reset Counter A
Resets Counter A to zero.
[61]
Reset Counter B
Resets Counter A to zero.
[70]
Start Timer 3
Starts timer 3, see par. 13-20
SL Controller Timer
for further description.
[71]
Start Timer 4
Starts timer 4, see par. 13-20
SL Controller Timer
for further description.
[72]
Start Timer 5
Starts timer 5, see par. 13-20
SL Controller Timer
for further description.
VLT
p
Automation VT Drive FC322
Programming Guide
2 Parameter Description
MG.20.W1.22 - VLT
p
is a registered Danfoss trademark
155
2