[1622]
Torque [%]
Shows the actual torque produced, in percentage.
[1630]
DC Link Voltage
Intermediate circuit voltage in the frequency converter.
[1632]
BrakeEnergy/s
Present brake power transferred to an external brake resistor.
Stated as an instantaneous value.
[1633]
BrakeEnergy/2 min
Brake power transferred to an external brake resistor. The mean power is calculated continuously
for the most recent 120 seconds.
[1634]
Heatsink Temp.
Present heat sink temperature of the frequency converter. The cut-out limit is 95 ±5 oC; cutting
back in occurs at 70 ±5° C.
[1635]
Thermal Drive Load
Percentage load of the inverters
[1636]
Inv. Nom. Current
Nominal current of the frequency converter
[1637]
Inv. Max. Current
Maximum current of the frequency converter
[1638]
SL Control State
State of the event executed by the control
[1639]
Control Card Temp.
Temperature of the control card.
[1650]
External Reference
Sum of the external reference as a percentage, i.e. the sum of analog/pulse/bus.
[1652]
Feedback [Unit]
Signal value in units from the programmed digital input(s).
[1653]
Digi Pot Reference
View the contribution of the digital potentiometer to the actual reference Feedback.
[1654]
Feedback 1 [Unit]
View the value of Feedback 1. See also par. 20-0*.
[1655]
Feedback 2 [Unit]
View the value of Feedback 2. See also par. 20-0*.
[1656]
Feedback 3 [Unit]
View the value of Feedback 3. See also par. 20-0*.
[1658]
PID Output [%]
Returns the Drive Closed Loop PID controller output value in percent.
[1659]
Adjusted Setpoint
Displays the actual operating set-point after it is modified by flow compensation. See parameters
22-8*.
[1660]
Digital Input
Displays the status of the digital inputs. Signal low = 0; Signal high = 1.
Regarding order, see par. 16-60. Bit 0 is at the extreme right.
[1661]
Terminal 53 Switch Setting
Setting of input terminal 53. Current = 0; Voltage = 1.
[1662]
Analog Input 53
Actual value at input 53 either as a reference or protection value.
[1663]
Terminal 54 Switch Setting
Setting of input terminal 54. Current = 0; Voltage = 1.
[1664]
Analog Input 54
Actual value at input 54 either as reference or protection value.
[1665]
Analog Output 42 [mA]
Actual value at output 42 in mA. Use par. 6-50 to select the variable to be represented by output
42.
[1666]
Digital Output [bin]
Binary value of all digital outputs.
[1667]
Freq. Input #29 [Hz]
Actual value of the frequency applied at terminal 29 as a pulse input.
[1668]
Freq. Input #33 [Hz]
Actual value of the frequency applied at terminal 33 as a pulse input.
[1669]
Pulse Output #27 [Hz]
Actual value of pulses applied to terminal 27 in digital output mode.
[1670]
Pulse Output #29 [Hz]
Actual value of pulses applied to terminal 29 in digital output mode.
[1671]
Relay Output [bin]
View the setting of all relays.
[1672]
Counter A
View the present value of Counter A.
[1673]
Counter B
View the present value of Counter B.
[1675]
Analog input X30/11
Actual value of the signal on input X30/11 (General Purpose I/O Card. Option)
[1676]
Analog input X30/12
Actual value of the signal on input X30/12 (General Purpose I/O Card. Optional)
[1677]
Analog output X30/8 [mA]
Actual value at output X30/8 (General Purpose I/O Card. Optional) Use Par. 6-60 to select the var-
iable to be shown.
[1680]
Fieldbus CTW 1
Control word (CTW) received from the Bus Master.
[1682]
Fieldbus REF 1
Main reference value sent with control word via the serial communications network e.g. from the
BMS, PLC or other master controller.