[199]
Pipe Filling
Active when the Pipe Fill function is operating. See par. 29-0*.
[200]
Full Capacity
All pumps running and at full speed
[201]
Pump1 Running
One or more of the pumps controlled by the Cascade Controller are running. The function will also
depend on the setting of in
Fixed Lead Pump
, par. 25-06. If set to
No
[0] Pump 1 refers to the pump
controlled by relay RELAY1 etc. If set to
Yes
[1] Pump 1 refers to the pump controlled by the
frequency converter only (without any of the build in relays involved) and Pump 2 to the pump
controlled by the relay RELAY1. See below table:
[202]
Pump2 Running
See [201]
[203]
Pump3 Running
See [201]
Setting in Par. 5-3*
Setting in Par. 25-06
[0] No
[1] Yes
[200] Pump 1 Running
Controlled by RELAY1
Frequency Converter controlled
[201] Pump 2 Running
Controlled by RELAY2
Controlled by RELAY1
[203] Pump 3 Running
Controlled by RELAY3
Controlled by RELAY2
5-30 Terminal 27 Digital Output
Option:
Function:
Same options and functions as par. 5-3*.
[0] *
No operation
5-31 Terminal 29 Digital Output
Option:
Function:
Same options and functions as par. 5-3*.
[0] *
No operation
5-32 Term X30/6 Digi Out (MCB 101)
Option:
Function:
[0] *
No operation
This parameter is active when option module MCB 101 is mounted in the frequency converter.
[1]
Control ready
The control board receives supply voltage.
[2]
Drive ready
The frequency converter is ready for operation and applies a supply signal on the control board.
[3]
Drive rdy/rem ctrl
The frequency converter is ready for operation and is in Auto On mode.
[4]
Stand-by / no warning
Ready for operation. No start or stop command is been given (start/disable). There are no warnings.
[5]
Running
Motor is running.
[6]
Running / no warning
Output speed is higher than the speed set in par. 1-81
Min Speed for Function at Stop [RPM]
. The
motor is running and there are no warnings.
[8]
Run on ref/no warn
Motor is running within the programmed current and speed ranges set in par. 4-50
Warning Current
Low
to par. 4-53
Warning Speed High
. There are no warnings.
[9]
Alarm
An alarm activates the output. There are no warnings.
[10]
Alarm or warning
An alarm or a warning activates the output.
[11]
At torque limit
The torque limit set in par. 4-16
Torque Limit Motor Mode
or par. 1-17 has been exceeded.
[12]
Out of current range
The motor current is outside the range set in par. 4-18
Current Limit
.
[13]
Below current, low
Motor current is lower than set in par. 4-50
Warning Current Low
.
[14]
Above current, high
Motor current is higher than set in par. 4-51
Warning Current High
.
VLT
p
Automation VT Drive FC322
Programming Guide
2 Parameter Description
MG.20.W1.22 - VLT
p
is a registered Danfoss trademark
83