TCNM-AD/EX/SP Family Software Configuration Parameter Guide
52
Bus Communication
NOTE
For further information regarding Fieldbus interfacing including downloadable support files, go to the
HMS website at http://www.anybus.com, choose the link to the support page, select the Anybus-
CompactCom product type and then your network type.
Baud Rate
This is a read-only parameter. The modules are set to use the automatic baud rate mechanism where the Fieldbus
Master defines the speed of the connection. After connection, for some Fieldbus types, the actual speed of the Fieldbus
will be displayed in this parameter.
For CC-Link Fieldbus, the Fieldbus Master does not set the network baud rate and therefore this parameter must be
set manually according to the application specific network baud rate.
Max. Exchange Area Size (Input+Output)
This is a read-only parameter. It defines the (fixed) maximum size of the exchange area (total of both Input and
Output Areas) available for messages between the Fieldbus Master and the Fieldbus module.
Selections:
Profibus
152
DeviceNet
152
Ethernet IP
152
CC-Link
254
CANopen
152
Profinet IO
64
Modbus TCP
152
Master Input Area Size
It defines the size of the message command sent from the Fieldbus module to the Fieldbus Master.
Selections:
Profibus
a value in the range
8 - 144
DeviceNet a value in the range
8 - 144
Ethernet IP a value in the range
8 - 144
* CC-Link a value in the range
2 - 126
CANopen
a value in the range
8 - 144
Profinet IO a value in the range
8 - 56
Modbus
TCP
a value in the range
8 - 144
* For CC-Link Version 1, the Master Input Area Size must be less than or equal to 30.
Master Output Area Size
It defines the size of the message command sent to the Fieldbus module from the Fieldbus Master.
Selections:
Profibus
a value in the range
8 - 144
DeviceNet a value in the range
8 - 144
Ethernet IP a value in the range
8 - 144
* CC-Link a value in the range
2 - 128
CANopen
a value in the range
8 - 144
Profinet IO a value in the range
8 - 56
Modbus
TCP
a value in the range
8 - 144
* For CC-Link Version 1, the Master Output Area Size must be less than or equal to 32.