TCNM-AD/EX/SP Family 
Software Configuration Parameter Guide 

  

  

  

 

Code Definition 

  

 

Operating Modes 

  

 

Reading System Layout 

  

 

Reading Parameters 

  

 

Data Communication Settings 

  

 

Digital I/O Setting 

  

 

LEDs & Keypad 

  

 

Display 

  

 

Diagnostics 

  

 

Statistics 

  

 

User Information Section 

  

  

  

SW package 001 and later 

  

September 30, 2013 

  

  

  

Summary of Contents for TCNM-AD Series

Page 1: ...arameter Guide Code Definition Operating Modes Reading System Layout Reading Parameters Data Communication Settings Digital I O Setting LEDs Keypad Display Diagnostics Statistics User Information Section SW package 001 and later September 30 2013 ...

Page 2: ...Main Serial Port Parameters 43 Auxiliary Serial Port 45 Heartbeat 45 Pass Through Options 47 Auxiliary Serial Port Parameters 47 TCNM ACBB5 Gateway 48 Line Parameters 49 Fieldbus 50 Heartbeat 50 Bus Communication 52 Digital I O Conditioning 54 TCP IP Services 55 UserSocket n 55 Heartbeat 56 Modbus TCP 57 Ethernet IP explicit messaging 58 Digital I O Setting 59 System Information Section 62 Device ...

Page 3: ...ollowing window appears asking the user to choose the desired configuration level The Wizard option is advised to new users since it shows a step by step scanner configuration Select the Create a new configuration button You will be guided through the configuration being asked to define the following parameters Barcode selection and definition ...

Page 4: ...TCNM AD EX SP Family Software Configuration Parameter Guide 2 Operating mode selection and definition Digital Outputs configuration Hardware interface selection ...

Page 5: ...ete the reader configuration as follows Saving the configuration to disk Switching to Advanced mode Sending the configuration to the scanner After sending the configuration to the scanner you have completed the configuration process By clicking Finish the System Information window will be displayed with specific information concerning the scanner ...

Page 6: ... serial interface In case of a failed reading phase no message is sent to the host computer Test Operating Mode This operating mode causes the reader to be continuously activated allowing to verify its reading features and its reading position with respect to the barcode For this reason it is particularly advised during the installation phase of the reader After 100 scans the values relative to an...

Page 7: ...nition and physical identification of a specific slave within network updates configuration to a file and makes it ready to be sent to the Master Express Network Setup automatically performs all the operations of the Network Wizard apart from the physical identification of a specific slave scanner NOTE Any updates or changes to the ID NET Master configuration cause the entire network to be reset T...

Page 8: ...r next to the Parameter Explorer window By repeatedly clicking the icon this area will be displayed or hidden Each scanner of the cluster is indicated by the following graphical objects check box allowing to select deselect a specific scanner to perform the desired operations i e program downloading icon representing the scanner status a label reporting information transmitted by the scanner when ...

Page 9: ...fault labels through the Express Network Setup Express Network Setup Before performing this procedure an ID NET address must be assigned to each slave scanner The most practical method is through the Net Autoset procedure Refer to the scanner Reference manual for details about alternative address assignment methods Once all addresses have been assigned the Express Network Setup is to be used when ...

Page 10: ...cedure of the current network The master and all slave scanners found will be represented in the Current Devices area Then select the desired slave scanner from the Current Devices area and click on the icon or drag and drop to transfer it to the Requested Devices area where your network customization is defined The following dialog box will appear allowing if necessary to change the slave address...

Page 11: ... using Show Device as a diagnostic tool on an already configured network the following notes apply If the Beam Shutter is Enabled the laser will not turn on Upon exit from Show Device the network returns to its previously configured state 3 If desired select the transferred added slave scanner within the Requested Devices area and click on the icon to customize the scanner label and slave address ...

Page 12: ...ame reading phase Code Collection In Code Collection mode expected codes are collected within a single reading phase in the order in which they are read The No Read message is produced only if none of the codes are read Up to 50 codes can be collected Logical Combination Rule It allows editing the rule which the combination of groups of labels is based upon Groups and their order define the output...

Page 13: ... Decoded Code Symbology Output Message Label 1 Label 2 Header Global No Read Message Terminator X Header Code 39 data Terminator X Header Code 128 data Terminator X X Header First decoded code Multiple Read Message string Terminator NOTE In case the Multiple Read Message is enabled and both codes are decoded the Multiple Read string will also be transmitted If the Multiple Read Message is disabled...

Page 14: ... DPS First decoded code Multiple Read Message string Terminator X X Header Code 93 data DPS EAN 8 data Terminator X X Header Code 93 data DPS UPC A data Terminator X X Header Interleaved 2 5 data DPS EAN 8 data Terminator X X Header Interleaved 2 5 data DPS UPC A data Terminator X X X X Header First decoded code Multiple Read Message string DPS First decoded code Multiple Read Message string Termi...

Page 15: ...ead By Different Scanners This parameter is available only when the Code Combination parameter is set to Code Collection and the scanner Topology Role is Master If enabled it allows transmitting all codes belonging to the same programmed Slot same symbology and content but read by different scanners including the Master in a single instance Codes Different When Scan Gap Is Greater Than This parame...

Page 16: ...nsmitted because their image does not match the expected code image Through the Decoding Severity parameter a ratio between the actual and the expected code image can be considered The lower this ratio is the higher the difference between the images can be However please note that setting a low value for this parameter increases the possibility of decoding errors Selections from 1 to 5 where 1 and...

Page 17: ...the minimum expected width of both quiet zones of the Addon portion of an EAN UPC barcode expressed in number of modules If the barcode quiet zones are less than the expected ratio the Addon barcode will not be decoded For the TCNM SP family if working in Reconstruction reading mode this parameter defines the minimum expected width of the ending Stop quiet zone of the Addon portion of an EAN UPC b...

Page 18: ...ional digits Label Length The label length in number of characters digits can be specified in order to be accepted for decoding Selections Variable all possible label lengths in number of characters digits allowed for the code selected are accepted Fixed from 1 to 60 only the selected length is accepted Fixed from 2 to 74 for GS1 DataBar Expanded only the selected length is accepted The selection ...

Page 19: ...ode symbology selected Code 39 Full ASCII from 29 to 619 a variable number of characters in steps of 10 whose range depends on the code symbology selected To select a particular barcode length in elements set Bar Count to the desired fixed value and Label Length to Variable 12 Code 128 Subset A 1234 Code 128 Subset C Digit Number variable Bar Count 31 Min Max Label Length Codes whose lengths are w...

Page 20: ...CII characters available in the list which appears by right clicking on the parameter edit box defining any string consisting of an undefined number of characters it may be empty identifying any character to be found in the position indicated within the string If your application requires inserting and NUL as characters it is necessary to use the following syntax character NUL character NUL NUL ch...

Page 21: ...ere in the scan line a particular code can be found The scan line is divided into 256 physical positions The code position is determined at the center of the label and is checked to be between the Min and Max parameters specified in the configuration These values go from 0 to 255 Selections a value from 0 to 255 Since the Min and Max values depend on many factors such as the scanner model number o...

Page 22: ...up is not read It is possible to define up to 15 no read strings corresponding to the 15 groups to be defined Local Multiple Read Strings This group allows defining a Local Multiple Read string for each group used in the Logical Combination Rule Group Label Local Multiple Read String n It defines the string to be transmitted when the expected label group is read more times than expected It is poss...

Page 23: ...sent and the no read event is risen at the end of the PS active phase On Line 2 Inputs the reading phase is defined by 2 inputs It starts when the Start Input is activated and stops when the Stop Input is deactivated unless the Extended Phase is enabled If the operation is successful the barcode characters are transmitted in the format defined during the configuration phase on the interface s enab...

Page 24: ...als the beginning of the reading phase Selections a character from NUL 00H to 7EH The Serial Start string must be different from the Serial Stop string and Motor ON OFF strings When ACK NAK Protocol or Energy Saving are enabled the Serial Start Stop Strings cannot contain ACK NAK characters Serial Stop String The Serial Stop string signals the end of the reading phase Selections a character from N...

Page 25: ...nuously scanning The reading phase is enabled when a barcode enters the reading zone of the scanner and is terminated after an N number of scans without a code where N is set using the Automatic Threshold selection The next reading phase will begin when a code enters the reading zone of the scanner again The N number of scans without a code must be selected to assure code identification in the rea...

Page 26: ...identical to the other operating modes except that there is no transmission on the serial port in case of a No Read condition For details about the conditions to use this operating mode see the Operating Mode Reference Table Continuous Threshold The Continuous Threshold sets an N number of scans without a code in order to accept same code consecutive reading This threshold does not apply to differ...

Page 27: ...formation about the reading performance of the laser beam and the code is continuously read After 100 scans the following information is transmitted on the serial interface The information can be displayed on the Host PC by running a terminal emulator program ex Hyper Terminal The information reports percentage of good reads code position in the scan line the code content code length ...

Page 28: ...decoded match the string saved in its memory It is valid when using On Line Automatic and Continuous Operating Modes If the code read matches the code verifier string then it is sent to the host through the configured port If it does not match the verifier string it can be sent or not depending on the Wrong Code Tx parameter Independently from the Wrong Code transmission a Wrong String message can...

Page 29: ...ase the input must be deactivated Selections from 1 to 2 Active Level Allows the selection of the active state of the input Selections Active Closed the input is active when current flows through IN pins Active Open the input is active when there is no current flowing through IN pins Right Code Tx When checked it enables the transmission of the Right Code Wrong Code Tx When checked it enables the ...

Page 30: ...types of scanners that will be connected together in the network as Slaves TCNM AD EX SP families To select this option it is necessary to disable the transmission on the Auxiliary Serial Port and enable it on the Main Serial Port through the corresponding Data Tx parameter Slave RS232 TypeA this selection is maintained for backward compatibility The slave configuration varies according to the typ...

Page 31: ...ff parameters to control the energy saving feature In particular it allows turning on off the motor and laser and if it is MASTER to turn on off all scanners on the network The time required to restart the system is only a few seconds independently from the number of scanners connected It is suggested to use this parameter for example when the it is not necessary to read codes for a lengthy period...

Page 32: ...s the Code Reading Condition parameter is toggled between the Standard and Difficult values In this way the scanner takes advantage of the two settings at each reading phase This is advisable when different reading conditions can occur TCNM EX Dark Background The scanner is optimized to read low contrast barcodes due to dark backgrounds Toggle In successive scan lines the Code Reading Condition pa...

Page 33: ... working in Reconstruction reading mode this parameter defines the minimum expected width of both the beginning Start and ending Stop barcode quiet zone expressed in number of modules The Start and Stop Ratios can be different from each other If the specific barcode quiet zone is less than the expected ratio the barcode will not be decoded Selections a value between 1 and 50 for TCNM SP Reconstruc...

Page 34: ... be restarted upon reset TCNM ACM OM110 Oscillating Mirror NOTE This parameter group is available only for TCNM AD EX family scanners with Oscillating Mirror Oscillating Mode This parameter defines the oscillating mode of the scanner mirror Selections Fixed the oscillating mirror deflects the scan line at a fixed angle of deflection 15 Continuous the scan line is deflected according to the Amplitu...

Page 35: ...eading zone Selections Fixed the oscillating mirror deflects the scan line at a fixed angle of deflection 15 Continuous the scan line is deflected according to the Second Zone Amplitude and Second Zone Frequency settings Second Zone Amplitude degrees This parameter is available only when working in Continuous Second Zone Oscillating Mode It defines the deflection range in degrees as a symmetrical ...

Page 36: ...rees This parameter is available only when working in Continuous oscillating mode It defines the maximum angle for the deflection range with respect to the angle perpendicular to the scanner 0 Selections a value from 5 to 35 Frequency Hz This parameter is available only when working in Continuous oscillating mode It defines the oscillating frequency in Hertz Selections a value from 0 2 to 20 0 Her...

Page 37: ...e scanner 0 The default value is 10 Selections a value from 5 to 35 Second Zone Min Angle degrees This parameter is available only when the second reading zone is working in Continuous Second Zone Oscillating Mode It defines the minimum angle for the second zone deflection range with respect to the angle perpendicular to the scanner 0 Selections a value from 5 to 35 Second Zone Max Angle degrees T...

Page 38: ...led While using the Crisplant protocol the value set for these parameters cannot be changed Crisplant Parameters This group allows defining all the parameters managing this communication protocol Crisplant Manufacturer ID It defines the Crisplant proprietary format Heartbeat Message It enables disables the transmission of the Heartbeat telegram Heartbeat Message Timing It defines the amount of tim...

Page 39: ...ion String is added to the No Read message string Message Tx Selection Message Tx Selection selects the transmission of the output message either on decoding or after the reading phase Selections On decoding After Reading Phase Off Delayed Tx Line only for On Line operating mode Physical Encoder This parameter is available only when Message Tx Selection is set to Delayed Tx Line If checked it enab...

Page 40: ...layed Tx Line Distance mm This parameter is available only when Message Tx Selection is set to Delayed Tx Line It defines the distance in mm delay from the Phase Off event to the TX line see Message Tx Selection NOTE The trigger LED on the scanner is activated at Phase Off independent from the Tx Line delay distance For local network configurations this delay starts after the Master Max Tx Delay A...

Page 41: ...ning direction with respect to the code direction can be defined Forward Direction String A Forward Direction string indicates that the current code has been scanned in the forward direction scanning from left to right This string is the default value can be customized by the user including up to 32 characters Selections characters from NUL 00H to 7EH Reverse Direction String A Reverse Direction s...

Page 42: ...ariable all possible code field lengths in number of characters digits allowed for the code selected are accepted Fixed only the length defined by the Code Field Length parameter is accepted Code Field Length This parameter is only available when the Code Field Length Setting is set to Fixed It defines in number of characters digits the length of the code field to be transmitted Selections a value...

Page 43: ...e of a message coming from Slave 3 through the Master MULTIDATA scanner or ID NET controller is represented below Address Header 03 Address Separator Slave 3 Header Code1 Code2 Coden Slave 3 Terminator Main Serial Port This option determines the communication between the scanner or in a multi sided layout between several scanners and a Host Data Tx If enabled checked data from the scanner will be ...

Page 44: ...rs Selections characters from NUL 00H to 7EH Counter Module This parameter enables a counter to track the number of Heartbeat messages Selections Disable no counter field in the Heartbeat message 10 counts cyclically from 0 to 9 100 counts cyclically from 0 to 99 1000 counts cyclically from 0 to 999 10000 counts cyclically from 0 to 9999 Custom allows defining a custom counter start stop range fro...

Page 45: ... Standard Standard is the normal mode for the Main Serial Interface In this communication mode the following physical connections are allowed RS232 RS485 full duplex Selecting Standard the scanner will send out the data using the specified Handshake but without any special protocol MUX32 Slave MUX32 slave is the communication mode used for connections to a Multiplexer For such a configuration the ...

Page 46: ...Communication Mode is selected it is possible to define an address for the connection of the scanner with a Multiplexer Selections a value from 0 to 31 Checksum If checked it enables the Checksum parameter It is a control byte of the communication protocol It is the one that distinguishes the normal protocol from the R version of the Siemens protocol itself 3964 from 3964R Priority Priority is a p...

Page 47: ... not sent on the Auxiliary Serial Port Data Tx disabled Selections Disable the Heartbeat message is not transmitted Enable Unconditioned the Heartbeat message is always transmitted even if communication is still active Enable Conditioned the Heartbeat message is transmitted only when there is no communication Pass Through It enables disables the Pass Through options Heartbeat The following paramet...

Page 48: ...parameter selects the starting counter value Selections a number from 0 to 9999 Counter Direction Sets the counter direction either up or down System Diagnostics If checked it enables the System Diagnostics Field in the Heartbeat message The System Diagnostics field is a fixed 2 byte field for the TCNM AD EX Family the second byte is always 0 The first byte has the following meaning 1 Reading Stat...

Page 49: ...port The terminator will be forwarded with the message 3 The Serial On Line Master Slave and Crisplant protocol parameters are not configurable for the Auxiliary interface String Max Length It defines the maximum length of the expected string to be received In case the string is longer than the one expected it will be discarded Termination String It defines the characters terminating the expected ...

Page 50: ... parameter configuration of either the Ethernet IP interface Fieldbus the Ethernet TCP IP Services which allow up to 2 User Sockets to be configured non Fieldbus or both IP Addressing in the Line Parameters branch determines the method of address selection either user defined Static Assignment DHCP or Remote Assignment CC Link Enables the Fieldbus branch to allow the CC Link interface parameters t...

Page 51: ...ctions Static Assignment the IP Address can be set manually through the IP_address IP_netmask and IP_gateway parameters DHCP the IP address is assigned by a DHCP server when getting the scanner configuration In this case the IP address parameters are read only and display the DHCP assigned address Remote Assignment the IP address is assigned by a remote network device PC using the IPConfig address...

Page 52: ...for TCP IP communications Data Tx If enabled checked data from the scanner will be transmitted on the Fieldbus network Heartbeat This parameter enables disables transmission of the Heartbeat message used to signal device or system status at regular intervals The Heartbeat message is independent from Data Tx and can be enabled even if data is not sent on the Fieldbus network Data Tx disabled Select...

Page 53: ...s the starting counter value Selections a number from 0 to 9999 Counter Direction Sets the counter direction either up or down System Diagnostics If checked it enables the System Diagnostics Field in the Heartbeat message The System Diagnostics field is a fixed 2 byte field for the TCNM AD EX Family the second byte is always 0 The first byte has the following meaning 1 Reading Station OK 3 Presenc...

Page 54: ...ut Areas available for messages between the Fieldbus Master and the Fieldbus module Selections Profibus 152 DeviceNet 152 Ethernet IP 152 CC Link 254 CANopen 152 Profinet IO 64 Modbus TCP 152 Master Input Area Size It defines the size of the message command sent from the Fieldbus module to the Fieldbus Master Selections Profibus a value in the range 8 144 DeviceNet a value in the range 8 144 Ether...

Page 55: ... max Node Address is 63 If the Input Area is greater than 14 or the Output Area is greater than 16 the max Node Address is 62 If the Input Area is greater than 22 or the Output Area is greater than 24 the max Node Address is 61 4 For CANopen the Node Address 128 forces the LSS Layer Setting Service which allows the Fieldbus Master to assign the baud rate and address but it is no longer possible to...

Page 56: ...tocols do not use Exchange Areas Digital Input Lines Input 1 Echo If checked the scanner Input 1 status is echoed to the Fieldbus Master via bit 0 in Byte 0 LSB of the Input Area For Ethernet IP under the TCP IP Services branch the Input 1 status is echoed to the Fieldbus Master using Assembly Object Instances Input 2 Echo If checked the scanner Input 2 status is echoed to the Fieldbus Master via ...

Page 57: ...the TCP IP User Socket Heartbeat This parameter enables disables transmission of the Heartbeat message used to signal device or system status at regular intervals The Heartbeat message is independent from Data Tx and can be enabled even if data is not sent on the TCP IP User Socket Data Tx disabled Selections Disable the Heartbeat message is not transmitted Enable Unconditioned the Heartbeat messa...

Page 58: ... Good Read No Read or Partial Read Master Diagnostic Check Period secs This parameter allows defining the period in seconds that WebSentinel will use to check for diagnostic errors on the Master scanner If an error is found it will be sent to WebSentinel Heartbeat The following parameters allow enabling the communication through the TCP IP interface protocol The Heartbeat message is used to signal...

Page 59: ... 3 Presence Sensor Failure 4 Reading Station Failure Network Diagnostics If checked it enables the Network Diagnostics Field in the Heartbeat message The Network Diagnostics field is a fixed 32 byte field one for each scanner in the network from scanner 0 Master to scanner 31 Each byte has the following meaning 0 Scanner not expected 1 Scanner OK 2 Scanner expected but not present not connected or...

Page 60: ... station tries a connection towards the server Server_address This parameter is available only when the Modbus TCP socket is configured as a Client It defines the IP address of the server to which the client tries to connect Start Register Number It defines the Starting Address field of the Modbus TCP message For details refer to Modicon Modbus Protocol Reference Guide by AEG Schneider Automation ...

Page 61: ...d I2B pins Debounce Filter ms Sets the maximum duration of the pulses which are rejected by the anti disturbance filter Pulses exceeding this limit are recognized as valid commands Selections 5 to 1000 ms Digital Output Lines Use Selection Local The scanner drives the output line depending on the activation deactivation events External Fieldbus The external Fieldbus Master drives the output line L...

Page 62: ... start event takes place starting the reading phase Phase Off the event occurs when a stop event takes place ending the reading phase Multiple Read the event occurs if a code is read more than once consecutively Right the event occurs if a code is successfully decoded and matches the Verifier Code Wrong the event occurs if a code is successfully decoded but does not match the Verifier Code Ready t...

Page 63: ...parameter Once this value is reached the counter is reset and starts recounting Selection value from 1 to 70000 NOTE This parameter is recommended only for On Line or Serial On Line operating modes Event Counter Mode Selection Consecutive This counter only counts events that occur in consecutive reading phases The output is activated after the Event Counter value is reached If the event is not con...

Page 64: ... Information This displays read only device identity information It can be visualized in GeniusPlus printed together with the configuration report and also through Host Mode Programming Detected Model Displays the reading device model number Serial Number Displays the reading device serial number ...

Page 65: ...or to select the output Tx Interface Selection Disable Test Mode Data Tx is disabled Main Test Mode Data Tx is enabled on the Main serial interface Aux Test Mode Data Tx is enabled on the Auxiliary serial interface Main Aux Test Mode Data Tx is enabled on the Main and Auxiliary serial interfaces NOTE You must not be in Test Mode activated by the Multifunction Key when configuring the scanner param...

Page 66: ...is parameter enables Network Status messages on the Master display for scanners with display and on the TCNM ACBB5 accessory display if present Toggle Network Status Monitor with Last Data Read Allows the Network Status Message to be toggled with the Last Data Read message on the Master display for scanners with display and on the TCNM ACBB5 accessory display if present Contrast Local Device This ...

Page 67: ...tus Selections Input_1 Input_2 Refresh Time It defines the frequency at which the diagnostic messages are updated This parameter excludes the network diagnostics which are updated at a fixed internal frequency LED Indication on Network Slave Failure This parameter has meaning only for a Master scanner since it allows the LEDs to signal a Network Slave Failure When enabled if a Slave Network Failur...

Page 68: ...oes not work Presence Sensor Stuck Timeout This parameter is available only when working in On Line operating mode and when the Conveyor Info is available It defines the time interval after which an error is generated if the status of the presence sensor does not change presence sensor remains open Selections Disable 1 sec 2 sec 5 sec 10 sec 30 sec 1 min Focus Displacement If checked it allows sen...

Page 69: ... allows sending an alarm whenever a checksum error has occurred on the oscillating mirror board EEPROM memory OSCILLATING MIRROR Data Write Error If checked it allows sending an alarm whenever a data write error has occurred to the oscillating mirror board EEPROM memory OSCILLATING MIRROR Communication Error If checked it allows sending an alarm whenever there is a communication error between the ...

Page 70: ...alarm whenever the input power to the scanner falls below an internal threshold which depends on the model TCNM SP 8 Vdc Operation at this level is not guaranteed and may reduce performance Fieldbus Failure If checked it allows sending an alarm whenever there is a communication error between the scanner and the Fieldbus module inside the TCNM ACBB5 connection box Fieldbus Configuration Error If ch...

Page 71: ... is not compatible with Fieldbus and or User Socket selections If a Fieldbus module is installed in the TCNM ACBB5 connection box the Main Interface selection will be ignored Message Position If Tx Mode is synchronous With Code the diagnostic messages will be transmitted on the same interface used for code transmission This selection determines if the diagnostic messages will replace the code be a...

Page 72: ... will be sent as Internal Numeric Message s or as User Defined String s If the Compact value is selected then only a single message will be sent in the User Defined Strings format In the case of multiple messages this will be the first one revealed If the first message is cleared then the next message if any will take its place Node Identification This parameter is meaningful only for devices set ...

Page 73: ...cillating mirror has not been recognized Oscillating Mirror Data Consistency Error For TCNM AD EX scanners it defines the message string up to 128 bytes that will be sent as a diagnostic message whenever a checksum error has occurred on the oscillating mirror onboard settings Start Stop Input Failure It defines the message string up to 128 bytes that will be sent as a diagnostic message whenever a...

Page 74: ...IZER Reset It defines the message string up to 128 bytes that will be sent as a diagnostic message whenever an unexpected analog board reset has occurred OSCILLATING MIRROR Motor Failure It defines the message string up to 128 bytes that will be sent as a diagnostic message whenever an oscillating mirror motor failure is signaled OSCILLATING MIRROR Motor Life End It defines the message string up t...

Page 75: ...will enter a sort of standby condition where the laser motor display and oscillating mirror for OM models are turned off until the internal temperature returns to within the normal operating range The Ready LED also blinks in this condition High Temperature Warning It defines the message string up to 128 bytes that will be sent as a diagnostic message whenever the internal temperature has reached ...

Page 76: ...ration error has occurred between the scanner and the Fieldbus module inside the TCNM ACBB5 connection box Fieldbus Mismatch It defines the message string up to 128 bytes that will be sent as a diagnostic message whenever the Fieldbus module inside the TCNM ACBB5 doesn t match the one saved in the scanner configuration memory Wrong TCNM ACBB Backup Module Rotary Switch Selection It defines the mes...

Page 77: ...ead Counter If enabled checked this counter is included in the statistical message and reports the total number of partial reads from the last hardware reset No Read Counter If enabled checked this counter is included in the statistical message and reports the total number of no reads from the last hardware reset Motor OFF Counter If enabled checked this counter is included in the statistical mess...

Page 78: ...ether with the scanner configuration It can be visualized in GeniusPlus printed together with the configuration report and also through Host Mode Programming User Name Add the User or Company name to the scanner information Device Name Add the Device Name to the scanner information Line Name Add the workstation Line Name or scanner position to the scanner information ...

Page 79: ...nternal threshold with respect to the programmed Frequency SP 98 OSCILLATING MIRROR Motor Life End the oscillating mirror motor has surpassed its factory declared functional life AD EX 99 Oscillating Mirror Data Consistency Error a checksum error has occurred on the oscillating mirror onboard settings SP 99 OSCILLATING MIRROR Data Consistency Error a checksum error has occurred on the oscillating ...

Page 80: ...ording to different conditions See also Note 2 Master only Diagnostic Error Number Meaning 1 Slave xx No Reply no response from slave number xx where xx is the slave address 64 Slave Address xx Duplication two or more slaves have the same address xx 80 Slave xx Net Configuration slave xx has been re configured NOTE 1 Errors 1 and 80 may be detected whenever any scanner configuration changes Error ...

Page 81: ...as occurred All 185 TCNM ACBB Backup Module Communication Failure there is a communication error between the scanner and the Backup module inside the TCNM ACBB connection box All 187 Wrong TCNM ACBB Backup Module Rotary Switch Selection one or more of the selected Backup module Rotary Switch settings inside the TCNM ACBB doesn t match the scanner configuration memory Some of these error messages m...

Page 82: ...the conveyor moves but both the presence sensors remain closed for more than the programmed No Phase timeout This message may indicate that no pack is present on the conveyor Furthermore it is assumed that both presence sensors are correctly synchronized otherwise a 131 or 133 error would be generated 133 PS Output Failure the conveyor moves and the PS Input is active while the PS Output is inacti...

Page 83: ...he topology role of the local scanner SYNCHRONIZED The Master SYNCHRONIZED Slave SYNCHRONIZED configuration is the traditional ID NET network configuration in which the On Line Operating Mode is used MULTIDATA The Master MULTIDATA Slave MULTIDATA configuration is an ID NET network configuration which allows the Slave scanners to be configured differently and independently from the Master In this w...

Page 84: ... does not require particular conditions Standard Message Format Information relative to code reading is transmitted in standard formats on the selected serial interface s The general format is HEADER DATA TERMINATOR The decoding result can be one of the following DECODED CODE NO READ WRONG READ Code Verifier DIAGNOSTIC MESSAGES A combination of the first two results can be obtained when using mult...

Page 85: ...hen the Code Field Length Setting parameter is Fixed the CODE FIELD is subject to the editing rules specified by the parameters Code Field Length Data Justification Fill Character No Read The No Read condition occurs whenever a code cannot be read or decoded during the reading phase Format For Disable No Read Message HEADER TERMINATOR For Single Label or Standard Multi Label when the Global No Rea...

Page 86: ...EAD CODE INFO FIELD if read but NOT Verifier Code Each field can appear or not depending on the configuration and the result of the reading Diagnostic Messages When enabled Diagnostic Messages can be sent as an output message for certain error conditions Format When Internal Numeric Messages are enabled HEADER DIAGNOSTIC HEADER INTERNAL NUMERIC MESSAGE DIAGNOSTIC TERMINATOR TERMINATOR where INTERN...

Page 87: ... Configuration Parameters regard parameters that are specific to the scanner These parameters are influenced by the Send Default and Send Configuration commands that is they are overwritten by these commands The same parameters are modified by the following Send with Options dialog from the Device Menu Environmental Parameters regard the scanner Identity and Position in a Network ID NET Master Sla...

Page 88: ... send the previously saved configuration both Configuration and Environmental parameters to the new scanner To do this select Send with Options from the Device Menu and check the Environmental Parameters checkbox In order to return a scanner to its absolute default parameters including Environmental parameters the following Send with Options dialog must be used ...

Page 89: ...ned by the finder program The port number is 51235 Then click OK 4 Perform a Device Get configuration from GeniusPlus NOTE Devices working in DHCP may be assigned different IP addresses at each powerup therefore steps 2 4 of the above procedure may need to be repeated at successive connections between GeniusPlus and the scanner Static IP Addressing DHCP Disabled 1 Printout the Setup Procedure Usin...

Page 90: ... the RS232 Serial Port enabled by default and the scanner Aux RS232 port 2 Perform a Device Get configuration from GeniusPlus 3 Set the Data Communication Setting TCNM ACBB5 Gateway Type to Ethernet TCP IP and the desired Line Parameters IP Addressing parameters 4 Send the configuration to the scanner 5 Set the GeniusPlus Tools Options Communications window to TCP IP and in the Device address or n...

Page 91: ...an be applied to any connected device through which backup memory is available regardless of the devices network configuration Backup Restore automatically checks whether a previous backup or configuration is already stored in backup memory for each device speeding up the procedure and making it more secure The Backup Restore function is supported by TCNM AD EX SP scanners when connected to or thr...

Page 92: ...t all scanner configurations will be overwritten 2 The Status window shows information as the restore procedure is being executed The Restore function also provides easy and secure Single Device Replacement 1 Remove the scanner to be replaced 2 Connect the new scanner make sure the new scanner has been previously set to default 3 Run the Restore procedure by pressing the Restore Button see Restore...