SRV-63 series AC servo drives Detailed parameter description
-146-
P4.92*
Restore to factory value
Setting range
Default
Unit
Available mode
0~1
0
-
P
S
T
F
After this operation, all parameters (P0~P6 group) can be restored to the default value.
Setting value
Function
[0]
Disabled
1
Enabled
P4.92*
Data size
16bit
Data format
DEC
Modbus address
1984,1985
CANopen address
0x245C,0x00
P4.93*
Reading enable of fault
record
Setting range
Default
Unit
Available mode
0~1
0
-
P
S
T
F
This parameter can set the enabling of reading the fault record.
Setting value
Function
[0]
Disabled
1
Enabled
P4.93*
Data size
16bit
Data format
DEC
Modbus address
1986,1987
CANopen address
0x245D,0x00
P4.94*
Clearing enable of fault
record
Setting range
Default
Unit
Available mode
0~1
0
-
P
S
T
F
This parameter can set the enabling of clearing the fault record.
Setting value
Function
[0]
Disabled
1
Enabled
P4.94*
Data size
16bit
Data format
DEC
Modbus address
1988,1989
CANopen address
0x245E,0x00
P4.95*
Group number of fault
record
Setting range
Default
Unit
Available mode
0~9
0
-
P
S
T
F
This parameter can set the group number of fault record.
0 corresponds to the group 1 fault recorded which is also the latest one, 9 corresponds to group
10 fault recorded which is also the earliest one.
P4.95*
Data size
16bit
Data format
DEC
Modbus address
1990,1991
CANopen address
0x245F,0x00
P4.96*
Factory parameters
Setting range
Default
Unit
Available mode
-
0
-
P
S
T
F
-
P4.96*
Data size
16bit
Data format
DEC
Modbus address
1992,1993
CANopen address
0x2460,0x00