SRV-63 series AC servo drives Detailed parameter description
-105-
with 0x11C or 0x01C (VS-SEL).
Relation with COM-:
0:OFF (the internal optical coupler corresponding to the input is not conducted);
1:ON (the internal optical coupler corresponding to the input is conducted).
P1.35
Data size
16bit
Data format
DEC
Modbus address
1270,1271
CANopen address
0x2123,0x00
P1.36
1
st
vibration control
frequency
Setting range
Default
Unit
Available mode
0.0~200.0
0.0
Hz
P
F
It is used to set the frequency point used to suppress the vibration at the peak of the load.
Note:
Invalid if the setting value is below 1.0Hz.
P1.36
Data size
16bit
Data format
DEC
Modbus address
1272,1273
CANopen address
0x2124,0x00
P1.37
1
st
vibration control filter
factor
Setting range
Default
Unit
Available mode
0.00~1.00
1.00
-
P
F
This parameter is used to set the filter factor of 1
st
vibration control filter.
P1.37
Data size
16bit
Data format
DEC
Modbus address
1274,1275
CANopen address
0x2125,0x00
P1.38
2
nd
vibration control
frequency
Setting range
Default
Unit
Available mode
0.0~200.0
0.0
Hz
P
F
P1.39
2
nd
vibration control filter
factor
Setting range
Default
Unit
Available mode
0.00~1.00
1.00
-
P
F
Please refer to P1.36 and P1.37 for the detailed information.
P1.38
Data size
16bit
Data format
DEC
Modbus address
1276,1277
CANopen address
0x2126,0x00
P1.39
Data size
16bit
Data format
DEC
Modbus address
1278,1279
CANopen address
0x2127,0x00
6.3 Motor control parameters (P2)
6.3.1 Gain setting
P2.00
1
st
speed gain
Setting range
Default
Unit
Available mode
0.1~3276.7
27.0
Hz
P
S
T
F
The responsiveness of the servo system speed loop is determined by the speed gain. When
increase the value of P2.00, the speed response will be improved, but it may easily cause
vibration and noise.
Note:
If the inertia ratio is set correctly, the unit of P2.00 is Hz.
P2.00
Data size
16bit
Data format
DEC
Modbus address
1400,1401
CANopen address
0x2200,0x00