IMinx
Operate time
Current
tx
txMin
IEC10000058
IEC10000058 V2 EN
Figure 182:
Minimum operate current and operate time for inverse time
characteristics
In order to fully comply with the curves definition, the setting parameter
txMin
shall
be set to the value which is equal to the operate time of the selected IEC inverse curve
for measured current of twenty times the set current pickup value. Note that the
operate time value is dependent on the selected setting value for time multiplier
kx
.
INxMult
: Multiplier for scaling of the current setting value. If a binary input signal
(ENMULTx) is activated, the current operation level is increased by this setting
constant.
ResetTypeCrvx
: The reset of the delay timer can be made in different ways. The
possibilities are described in the technical reference manual.
tResetx
: Constant reset time delay in s for step x.
HarmBlockx
: This is used to enable block of step x from 2
nd
harmonic restrain
function.
tPCrvx, tACrvx, tBCrvx, tCCrvx
: Parameters for user programmable of inverse time
characteristic curve. The time characteristic equation is according to equation
:
[ ]
=
+
×
-
>
æ
ö
ç
÷
ç
÷
ç
÷
æ
ö
ç
÷
ç
÷
è
ø
è
ø
p
A
t s
B k
i
C
in
EQUATION1189 V1 EN
(Equation 192)
Further description can be found in the technical reference manual.
Section 9
1MRK 502 071-UEN -
Current protection
346
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
Application manual
Summary of Contents for Relion REG670
Page 1: ...RELION 670 SERIES Generator protection REG670 Version 2 2 IEC Application manual...
Page 2: ......
Page 108: ...102...
Page 132: ...126...
Page 324: ...318...
Page 442: ...436...
Page 476: ...470...
Page 628: ...622...
Page 718: ...712...
Page 728: ...722...
Page 768: ...762...
Page 778: ...772...
Page 779: ...773...