Name of OUTx
Type
Description
Value when
activated
Value when
deactivated
OUT9
BOOLEAN
Output 9
256
0
OUT10
BOOLEAN
Output 10
512
0
OUT11
BOOLEAN
Output 11
1024
0
OUT12
BOOLEAN
Output 12
2048
0
OUT13
BOOLEAN
Output 13
4096
0
OUT14
BOOLEAN
Output 14
8192
0
OUT15
BOOLEAN
Output 15
16384
0
OUT16
BOOLEAN
Output 16
32768
0
The sum of the numbers in column “Value when activated” when all OUTx (1≤x≤16)
are active equals 65535. This is the highest integer that can be converted by the
ITBGAPC function block.
16.12
Pulse integrator TIGAPC
16.12.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Pulse integrator
TIGAPC
16.12.2
Application
The pulse integrator function TIGAPC is intended for applications where there is a
need for a integration of a pulsed signal. For example, the pulses from the start output
of certain functions, like reverse power, loss of excitation and pole slip. Some
applications may require the integration of the start output of those functions to
perform the trip.
16.12.3
Setting guidelines
The pulse integrator function provides settings for time delay to operate and time
delay to reset. The time delay to operate setting is evaluated for activation of the output
and there will be no output until the integration of the input pulses equals this setting.
The output will be deactivated when the input signal is deactivated and the time delay
to reset has elapsed.
Section 16
1MRK 502 071-UEN -
Logic
616
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
Application manual
Summary of Contents for Relion REG670
Page 1: ...RELION 670 SERIES Generator protection REG670 Version 2 2 IEC Application manual...
Page 2: ......
Page 108: ...102...
Page 132: ...126...
Page 324: ...318...
Page 442: ...436...
Page 476: ...470...
Page 628: ...622...
Page 718: ...712...
Page 728: ...722...
Page 768: ...762...
Page 778: ...772...
Page 779: ...773...