IEC140000119-2-en.vsd
IEC140000119 V2 EN
Figure 40:
Multiple instances of PHASORREPORT blocks
shows both instances of ANALOGREPORT function blocks. The instance
number is visible in the bottom of each function block. For each instance, there are
three separate ANALOGREPORT blocks capable of reporting up to 24 Analog
signals (8 Analog signals in each ANALOGREPORT block). These can include for
example transfer of active and reactive power or reporting the milliampere input
signals to the PDC clients as defined in IEEE C37.118 data frame format.
IEC140000120-2-en.vsd
IEC140000120 V2 EN
Figure 41:
Multiple instances of ANALOGREPORT blocks
shows both instances of BINARYREPORT function blocks. The instance
number is visible in the bottom of each function block. For each instance, there are
three separate BINARYREPORT blocks capable of reporting up to 24 Binary signals
(8 Binary signals in each BINARYREPORT block). These binary signals can be for
example dis-connector or breaker position indications or internal/external protection
alarm signals.
1MRK 502 071-UEN -
Section 6
Wide area measurement system
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
109
Application manual