CT 300/5
in Delta
(DAC)
CT 800/5
Star
20.9 MVA
69/12.5 kV
YNd1
(YD
AC
)
CT 300/5
Star
CT 800/5
Star
20.9 MVA
69/12.5 kV
YNd1
(YD
AC
)
en06000554.vsd
IEC06000554 V1 EN
Figure 55:
Two differential protection solutions for star-delta connected power
transformer
For this particular power transformer the 69 kV side phase-to-earth no-load voltages
lead by 30 degrees the 12.5 kV side phase-to- earth no-load voltages. Thus when
external phase angle shift compensation is done by connecting main HV CTs in delta,
as shown in the right-hand side in figure
, it must be ensured that the HV currents
are rotated by 30° in clockwise direction. Thus the DAC delta CT connection must be
used for 69 kV CTs in order to put 69 kV & 12.5 kV currents in phase.
To ensure proper application of the IED for this power transformer it is necessary to
do the following:
1. Check that HV & LV CTs are connected to 5 A CT inputs in the IED.
2. For second solution make sure that HV delta connected CTs are DAC connected.
3. For star connected CTs make sure how they are stared (that is, earthed) to/from
protected transformer.
4. Enter the following settings for all three CT input channels used for the LV side CTs
see table
.
Section 7
1MRK 502 071-UEN -
Differential protection
140
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
Application manual
Summary of Contents for Relion REG670
Page 1: ...RELION 670 SERIES Generator protection REG670 Version 2 2 IEC Application manual...
Page 2: ......
Page 108: ...102...
Page 132: ...126...
Page 324: ...318...
Page 442: ...436...
Page 476: ...470...
Page 628: ...622...
Page 718: ...712...
Page 728: ...722...
Page 768: ...762...
Page 778: ...772...
Page 779: ...773...