Operation
FSDMode
: This setting enables/disables the fast step down function. Enabling can be
for automatic and manual control, or for only automatic control alternatively.
tFSD
: Time delay to be used for the fast step down tapping.
Voltage
UseCmdUSet
: This setting enabled makes it possible to set the target voltage level via
IEC 61850 set point command. This, in turn, makes the setting
USet
redundant.
USet
: Setting value for the target voltage, to be set in percent of
UBase
.
UDeadband
: Setting value for one half of the outer deadband, to be set in percent of
UBase
. The deadband is symmetrical around
USet
, see section
control for a single transformer"
. In that figure
UDeadband
is equal to
D
U.
The setting is normally selected to a value near the power transformer’s tap changer
voltage step (typically 75 - 125% of the tap changer step).
UDeadbandInner
: Setting value for one half of the inner deadband, to be set in percent
of
UBase
. The inner deadband is symmetrical around
USet
, see section
voltage control for a single transformer"
. In that figure
UDeadbandInner
is
equal to
D
U
in
. The setting shall be smaller than
UDeadband
. Typically the inner
deadband can be set to 25-70% of the
UDeadband
value.
Umax
: This setting gives the upper limit of permitted busbar voltage (see section
"Automatic voltage control for a single transformer"
, figure
). It is set in percent of
UBase
. If
OVPartBk
is set to
Auto&ManBlock
, then busbar voltages above
Umax
will
result in a partial blocking such that only lower commands are permitted.
Umin
This setting gives the lower limit of permitted busbar voltage (see section
"Automatic voltage control for a single transformer"
, figure
). It is set in percent of
UBase
. If
UVPartBk
is set to
Auto Block
or
Auto&ManBlock
, then busbar voltages
below
Umin
will result in a partial blocking such that only raise commands are
permitted.
Ublock
: Voltages below
Ublock
normally correspond to a disconnected transformer
and therefore it is recommended to block automatic control for this condition (setting
UVBk
).
Ublock
is set in percent of
UBase
.
Time
t1Use
: Selection of time characteristic (definite or inverse) for
t1
.
t1
: Time delay for the initial (first) raise/lower command.
t2Use
: Selection of time characteristic (definite or inverse) for
t2
.
t2
: Time delay for consecutive raise/lower commands. In the circulating current
method, the second, third, etc. commands are all executed with time delay
t2
independently of which transformer in the parallel group that is tapping. In the master-
Section 15
1MRK 502 071-UEN -
Control
582
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
Application manual
Summary of Contents for Relion REG670
Page 1: ...RELION 670 SERIES Generator protection REG670 Version 2 2 IEC Application manual...
Page 2: ......
Page 108: ...102...
Page 132: ...126...
Page 324: ...318...
Page 442: ...436...
Page 476: ...470...
Page 628: ...622...
Page 718: ...712...
Page 728: ...722...
Page 768: ...762...
Page 778: ...772...
Page 779: ...773...