en06000519-2.vsd
IEC06000519 V2 EN
Figure 340:
Direct fibre optical connection between two IEDs with LDCM
The LDCM can also be used together with an external optical to galvanic G.703
converter as shown in figure
. These solutions are aimed for connections to a
multiplexer, which in turn is connected to a telecommunications transmission
network (for example PDH).
Telecom. Network
*)
*)
Multiplexer
Multiplexer
en05000527-2.vsd
*) Converting optical to galvanic G.703
IEC05000527 V2 EN
Figure 341:
LDCM with an external optical to galvanic converter and a multiplexer
When an external modem G.703 is used, the connection between LDCM and the
modem is made with a multimode fibre of max. 3 km length. The IEEE/ANSI C37.94
protocol is always used between LDCM and the modem.
21.1.3
Setting guidelines
64 kbit and 2 Mbit mode common settings
ChannelMode
defines how an IED discards the LDCM information when one of the
IEDs in the system is out of service: it can either be done on the IED out of service by
setting all local LDCMs to channel mode
OutOfService
or at the remote end by setting
1MRK 502 071-UEN -
Section 21
Remote communication
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
715
Application manual
Summary of Contents for Relion REG670
Page 1: ...RELION 670 SERIES Generator protection REG670 Version 2 2 IEC Application manual...
Page 2: ......
Page 108: ...102...
Page 132: ...126...
Page 324: ...318...
Page 442: ...436...
Page 476: ...470...
Page 628: ...622...
Page 718: ...712...
Page 728: ...722...
Page 768: ...762...
Page 778: ...772...
Page 779: ...773...