110kV Busbar
200/1
35 / 0,1
kV
35kV Busbar
500/5
P
Q
31,5 MVA
110/36,75/(10,5) kV
Yy0(d5)
U
L1L2
IEC09000040-1-en.vsd
IED
IEC09000040-1-EN V1 EN
Figure 310:
Single line diagram for transformer application
In order to measure the active and reactive power as indicated in figure
, it is
necessary to do the following:
1. Set correctly all CT and VT and phase angle reference channel
PhaseAngleRef
data using PCM600 for analog input channels
2. Connect, in PCM600, measurement function to LV side CT & VT inputs
3. Set the setting parameters for relevant Measurement function as shown in the
Section 17
1MRK 502 071-UEN -
Monitoring
632
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
Application manual