³
=
+
142
ALF
17.8
3 5
EQUATION2540 V2 EN
(Equation 297)
CTs with the following data will fulfil the requirements for the generator differential
protection in this application:
•
Class 5P20 (5P18), 5 VA and R
ct
< 3 Ω.
It shall be noted that even if the rated burden of this CT is specified to 5 VA it is not
possible to have an actual burden more than 2.8 Ω and still fulfil the CT requirements.
It is of course also possible to specify the CT according to other classes. For example
a CT with the following data will also fulfil the requirements:
•
Class PX, R
CT
< 3 Ω and the knee point e.m.f.
³
×
=
×
=
k
al
E
0.8 E
0.8 142 114 V
EQUATION2541 V2 EN
(Equation 298)
As an alternative it can be suitable to provide the CT manufacturer with the data
according to equation
(
)
(
)
³
=
×
×
+
+
=
×
× ×
+
NG
al
alreqRat
sr
ct
w
addbu
ct
pr
I
3250
E
E
30
I
R
R
R
30
1 R
2,8
I
4000
EQUATION2542 V2 EN
(Equation 299)
(
)
³
×
×
+
+
³
×
× =
+
al
NG
sr
CT
w
addbu
pr
al
CT
E
I
30
I
R
R
R
I
E
3250
30
1 24.4
R
2.8
4000
EQUATION2543 V2 EN
(Equation 300)
This can give the CT manufacturer a possibility to optimize the relation between the
resistance of the CT winding and the area of the iron core.
If the CT shall be specified as a class PX the following relation between the knee point
e.m.f. E
k
and R
ct
shall be fulfilled:
(
)
³
³
×
+
+
k
k
ct
ct
E
E
24.4
or
19.5
0.8 R
2.8
R
2.8
EQUATION2544 V2 EN
(Equation 301)
Section 24
1MRK 502 071-UEN -
Requirements
752
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
Application manual
Summary of Contents for Relion REG670
Page 1: ...RELION 670 SERIES Generator protection REG670 Version 2 2 IEC Application manual...
Page 2: ......
Page 108: ...102...
Page 132: ...126...
Page 324: ...318...
Page 442: ...436...
Page 476: ...470...
Page 628: ...622...
Page 718: ...712...
Page 728: ...722...
Page 768: ...762...
Page 778: ...772...
Page 779: ...773...