The connections are similar in all SESRSYN functions, apart from the breaker
position indications. The physical analog connections of voltages and the connection
to the IED and SESRSYN function blocks must be carefully checked in PCM600. In
all SESRSYN functions the connections and configurations must abide by the
following rules: Normally apparatus position is connected with contacts showing both
open (b-type) and closed positions (a-type).
WA1_QA1:
•
B1QOPEN/CLD = Position of TIE_QA1 breaker and belonging disconnectors
•
B2QOPEN/CLD = Position of WA2_QA1 breaker and belonging disconnectors
•
LN1QOPEN/CLD = Position of LINE1_QB9 disconnector
•
LN2QOPEN/CLD = Position of LINE2_QB9 disconnector
•
UB1OK/FF = Supervision of WA1_MCB fuse
•
UB2OK/FF = Supervision of WA2_MCB fuse
•
ULN1OK/FF = Supervision of LINE1_MCB fuse
•
ULN2OK/FF = Supervision of LINE2_MCB fuse
•
Setting
CBConfig
=
1 1/2 bus CB
TIE_QA1:
•
B1QOPEN/CLD = Position of WA1_QA1 breaker and belonging disconnectors
•
B2QOPEN/CLD = Position of WA2_QA1 breaker and belonging disconnectors
•
LN1QOPEN/CLD = Position of LINE1_QB9 disconnector
•
LN2QOPEN/CLD = Position of LINE2_QB9 disconnector
•
UB1OK/FF = Supervision of WA1_MCB fuse
•
UB2OK/FF = Supervision of WA2_MCB fuse
•
ULN1OK/FF = Supervision of LINE1_MCB fuse
•
ULN2OK/FF = Supervision of LINE2_MCB fuse
•
Setting
CBConfig
=
Tie CB
WA2_QA1:
•
B1QOPEN/CLD = Position of WA1_QA1 breaker and belonging disconnectors
•
B2QOPEN/CLD = Position of TIE_QA1 breaker and belonging disconnectors
•
LN1QOPEN/CLD = Position of LINE1_QB9 disconnector
•
LN2QOPEN/CLD = Position of LINE2_QB9 disconnector
•
UB1OK/FF = Supervision of WA1_MCB fuse
•
UB2OK/FF = Supervision of WA2_MCB fuse
•
ULN1OK/FF = Supervision of LINE1_MCB fuse
•
ULN2OK/FF = Supervision of LINE2_MCB fuse
•
Setting
CBConfig
=
1 1/2 bus alt. CB
If only two SESRSYN functions are provided in the same IED, the connections and
settings are according to the SESRSYN functions for WA1_QA1 and TIE_QA1.
Section 15
1MRK 502 071-UEN -
Control
490
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
Application manual
Summary of Contents for Relion REG670
Page 1: ...RELION 670 SERIES Generator protection REG670 Version 2 2 IEC Application manual...
Page 2: ......
Page 108: ...102...
Page 132: ...126...
Page 324: ...318...
Page 442: ...436...
Page 476: ...470...
Page 628: ...622...
Page 718: ...712...
Page 728: ...722...
Page 768: ...762...
Page 778: ...772...
Page 779: ...773...