tZ1
:
tZ1
is the setting of trip delay for Z1 and this parameter is recommended to set 0.1
s.
© ABB Group
June 21, 2010 | Slide 1
IEC10000201-1-en.vsd
IEC10000201 V1 EN
Figure 152:
Loss of excitation characteristics recommended by IEEE
It is recommended to set
XoffsetZ2
equal to - X
d
'/2 and
Z2diamater
equal to
X
d
.
tZ2
:
tZ2
is the setting of trip delay for Z2 and this parameter is recommended to set 2.0
s not to risk unwanted trip at oscillations with temporary apparent impedance within
the characteristic.
DirSuperv
: The directional restrain characteristic allows impedance setting with
positive X value without the risk of unwanted operation of the under-excitation
function. To enable the directional restrain option the parameter
DirSuperv
shall be set
On
.
XoffsetDirLine
,
DirAngle
: The settings
XoffsetDirLine
and
DirAngle
are shown in
figure
XoffsetDirLine
is set in % of the base impedance according to
.
XoffsetDirLine
is given a positive value if X > 0.
DirAngle
is set in degrees with
negative value in the 4
th
quadrant. Typical value is -13°.
1MRK 502 071-UEN -
Section 8
Impedance protection
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
289
Application manual
Summary of Contents for Relion REG670
Page 1: ...RELION 670 SERIES Generator protection REG670 Version 2 2 IEC Application manual...
Page 2: ......
Page 108: ...102...
Page 132: ...126...
Page 324: ...318...
Page 442: ...436...
Page 476: ...470...
Page 628: ...622...
Page 718: ...712...
Page 728: ...722...
Page 768: ...762...
Page 778: ...772...
Page 779: ...773...