) 100
s
IN
I
IBase
IECEQUATION17003 V1 EN
(Equation 191)
Transformer inrush current shall be considered.
The setting of the protection is set as a percentage of the base current (
IBase
).
Operation
: set the protection to
On
or
Off
.
IN>>
: Set operate current in % of
IB
.
IN>>Max
and
IN>>Min
should only be changed if remote setting of operation
current level,
IN>>
, is used. The limits are used for decreasing the used range of the
IN>>
setting. If
IN>>
is set outside
IN>>Max
and
IN>>Min
, the closest of the limits
to
IN>>
is used by the function. If
IN>>Max
is smaller than
IN>>Min
, the limits are
swapped.
StValMult
: The set operate current can be changed by activation of the binary input
ENMULT to the set factor
StValMult
.
9.4
Directional residual overcurrent protection, four steps
EF4PTOC
9.4.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Directional residual overcurrent
protection, four steps
EF4PTOC
4(IN>)
4
alt
4
TEF-REVA V2 EN
51N_67N
9.4.2
Application
The directional residual overcurrent protection, four steps EF4PTOC is used in
several applications in the power system. Some applications are:
Section 9
1MRK 502 071-UEN -
Current protection
338
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
Application manual
Summary of Contents for Relion REG670
Page 1: ...RELION 670 SERIES Generator protection REG670 Version 2 2 IEC Application manual...
Page 2: ......
Page 108: ...102...
Page 132: ...126...
Page 324: ...318...
Page 442: ...436...
Page 476: ...470...
Page 628: ...622...
Page 718: ...712...
Page 728: ...722...
Page 768: ...762...
Page 778: ...772...
Page 779: ...773...