Similarly for Signed comparison between inputs
Set the
EnaAbs
=
Signed
Set the
RefSource
=
Input REF
For absolute comparison between input and setting
Set the
EnaAbs
=
Absolute
Set the
RefSource
=
Set Value
SetValue
shall be set between -2000000000 to 2000000000
Similarly for signed comparison between input and setting
Set the
EnaAbs
=
Signed
Set the
RefSource
=
Set Value
SetValue
shall be set between -2000000000 to 2000000000
16.15
Comparator for real inputs - REALCOMP
16.15.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Comparator for real inputs
REALCOMP
Real<=>
16.15.2
Application
The function gives the possibility to monitor the level of real values in the system
relative to each other or to a fixed value. It is a basic arithmetic function that can be
used for monitoring, supervision, interlocking and other logics.
16.15.3
Setting guidelines
Setting procedure on the IED:
EnaAbs
: This setting is used to select the comparison type between signed and
absolute values.
•
Absolute
: Comparison is performed with absolute values of input and reference.
•
Signed
: Comparison is performed with signed values of input and reference.
1MRK 502 071-UEN -
Section 16
Logic
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
619
Application manual
Summary of Contents for Relion REG670
Page 1: ...RELION 670 SERIES Generator protection REG670 Version 2 2 IEC Application manual...
Page 2: ......
Page 108: ...102...
Page 132: ...126...
Page 324: ...318...
Page 442: ...436...
Page 476: ...470...
Page 628: ...622...
Page 718: ...712...
Page 728: ...722...
Page 768: ...762...
Page 778: ...772...
Page 779: ...773...