3)
are three connections made in the Signal Matrix tool (SMT), Application configuration tool
(ACT), which connects these three voltage inputs to first three input channels of the
preprocessing function block 5). Depending on the type of functions, which need this voltage
information, more than one preprocessing block might be connected in parallel to these three
VT inputs
4)
shows that in this example the fourth (that is, residual) input channel of the preprocessing
block is not connected in SMT. Note. If the parameters U
L1
, U
L2
, U
L3
, U
N
should be used the
open delta must be connected here.
5)
Preprocessing block has a task to digitally filter the connected analog inputs and calculate:
•
fundamental frequency phasors for all four input channels
•
harmonic content for all four input channels
•
positive, negative and zero sequence quantities by using the fundamental frequency
phasors for the first three input channels (channel one taken as reference for sequence
quantities)
These calculated values are then available for all built-in protection and control functions
within the IED, which are connected to this preprocessing function block in the configuration
tool. For this application most of the preprocessing settings can be left to the default values.
However the following settings shall be set as shown here:
ConnectionType=Ph-Ph
UBase=13.8 kV
If frequency tracking and compensation is required (this feature is typically required only for
IEDs installed in the generating stations) then the setting parameters
DFTReference shall be
set accordingly.
4.2.4.5
Example on how to connect an open delta VT to the IED for high
impedance earthed or unearthed networks
gives an example about the wiring of an open delta VT to the IED for high
impedance earthed or unearthed power systems. It shall be noted that this type of VT
connection presents a secondary voltage proportional to 3U0 to the IED.
In case of a solid earth fault close to the VT location the primary value of 3Uo will be
equal to:
3 0
3
3
Ph Ph
Ph N
U
U
U
-
-
=
×
= ×
EQUATION1921 V3 EN
(Equation 3)
The primary rated voltage of an open Delta VT is always equal to U
Ph-E
. Three series
connected VT secondary windings gives a secondary voltage equal to three times the
individual VT secondary winding rating. Thus the secondary windings of open delta
VTs quite often have a secondary rated voltage equal to one third of the rated phase-
to-phase VT secondary voltage (110/3V in this particular example).
gives overview of required actions by the user in order to make this
measurement available to the built-in protection and control functions within the IED
as well.
Section 4
1MRK 502 071-UEN -
Analog inputs
86
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
Application manual
Summary of Contents for Relion REG670
Page 1: ...RELION 670 SERIES Generator protection REG670 Version 2 2 IEC Application manual...
Page 2: ......
Page 108: ...102...
Page 132: ...126...
Page 324: ...318...
Page 442: ...436...
Page 476: ...470...
Page 628: ...622...
Page 718: ...712...
Page 728: ...722...
Page 768: ...762...
Page 778: ...772...
Page 779: ...773...