Setting parameter
selected value for both Solution 1
(star conected CT)
Selected value for both Solution
2 (delta connected CT)
ConnectTypeW1
Delta (D)
STAR (Y)
1)
ConnectTypeW2
star=y
star=y
ClockNumberW2
1 [30 deg lag]
0 [0 deg]
1)
ZSCurrSubtrW1
Off
Off
ZSCurrSubtrW2
On
On
2)
TconfigForW1
No
No
TconfigForW2
No
No
LocationOLTC1
Not Used
Not Used
Other parameters
Not relevant for this application.
Use default value.
Not relevant for this
application. Use default value.
1)
To compensate for delta connected CTs.
2)
Zero-sequence current is already removed by connecting main CTs in delta.
Star-star connected power transformer with load tap changer and
tertiary not loaded delta winding
Single line diagrams for two possible solutions for such type of power transformer
with all relevant application data are given in figure
example is applicable for protection of autotransformer with not loaded tertiary delta
winding as well.
CT 500/5
Star
31.5/31.5/(10.5) MVA
110±11×1.5% /36.75/(10.5) kV
YNyn0(d5)
CT 200/1
Star
CT 500/5
in Delta
(DAB)
31.5/31.5/(10.5) MVA
110±11×1.5% /36.75/(10.5) kV
YNyn0(d5)
CT 200/1
in Delta
(DAB)
en06000558.vsd
IEC06000558 V1 EN
Figure 57:
Two differential protection solutions for star-star connected
transformer.
Section 7
1MRK 502 071-UEN -
Differential protection
144
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
Application manual
Summary of Contents for Relion REG670
Page 1: ...RELION 670 SERIES Generator protection REG670 Version 2 2 IEC Application manual...
Page 2: ......
Page 108: ...102...
Page 132: ...126...
Page 324: ...318...
Page 442: ...436...
Page 476: ...470...
Page 628: ...622...
Page 718: ...712...
Page 728: ...722...
Page 768: ...762...
Page 778: ...772...
Page 779: ...773...