Where:
1)
shows how to connect the secondary side of open delta VT to one VT input in the IED.
+3Uo shall be connected to the IED.
2)
is TRM where this voltage input is located. It shall be noted that for this voltage input the
following setting values shall be entered:
138
3
138
3
VTprim
kV
=
×
=
EQUATION1928 V1 EN
(Equation 8)
115
sec
3
115
3
VT
V
=
×
=
EQUATION1929 V1 EN
(Equation 9)
Inside the IED, only the ratio of these two parameters is used. It shall be noted that the
ratio of the entered values exactly corresponds to ratio of one individual open delta VT.
138
138
3
115
115
3
=
EQUATION1930 V1 EN
(Equation 10)
3)
shows that in this example the first three input channel of the preprocessing block is not
connected in SMT tool.
4)
shows the connection made in Signal Matrix Tool (SMT), which connect this voltage
input to the fourth input channel of the preprocessing function block 4).
5)
preprocessing block has a task to digitally filter the connected analog inputs and
calculate:
•
fundamental frequency phasors for all four input channels
•
harmonic content for all four input channels
•
positive, negative and zero sequence quantities by using the fundamental
frequency phasors for the first three input channels (channel one taken as
reference for sequence quantities)
These calculated values are then available for all built-in protection and control functions
within the IED, which are connected to this preprocessing function block in the
configuration tool. For this application most of the preprocessing settings can be left to
the default values.
If frequency tracking and compensation is required (this feature is typically required only
for IEDs installed in the generating stations) then the setting parameters
DFTReference
shall be set accordingly.
4.2.4.7
Example on how to connect a neutral point VT to the IED
gives an example on how to connect a neutral point VT to the IED. This type
of VT connection presents secondary voltage proportional to U
0
to the IED.
Section 4
1MRK 502 071-UEN -
Analog inputs
90
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
Application manual
Summary of Contents for Relion REG670
Page 1: ...RELION 670 SERIES Generator protection REG670 Version 2 2 IEC Application manual...
Page 2: ......
Page 108: ...102...
Page 132: ...126...
Page 324: ...318...
Page 442: ...436...
Page 476: ...470...
Page 628: ...622...
Page 718: ...712...
Page 728: ...722...
Page 768: ...762...
Page 778: ...772...
Page 779: ...773...