These settings, two per zone (x=1,2..5&RV), with options {Off, Quadrilateral, Mho,
Offset}, are used to set the operation and characteristic for phase-to-earth and phase-
to-phase faults, respectively.
For example, in one zone it is possible to choose Mho characteristic for the three Ph-
Ph measuring loops and Quadrilateral characteristic for the three Ph-E measuring
loops.
DirModeZx
This setting defines the operating direction for zones Z3, Z4 and Z5 (the directionality
of zones Z1, Z2 and ZRV is fixed). The options are
Non-directional
,
Forward
or
Reverse
. The result from respective set value is illustrated in figure
, where the
positive impedance corresponds to the direction out on the protected line.
IEC05000182-2-en.vsdx
R
X
R
X
R
X
Non-directional
Forward
Reverse
IEC05000182 V2 EN
Figure 93:
Directional operating modes of the distance measuring zones 3 to 5
tPPZx
,
tPEZx
,
TimerModeZx
,
ZoneLinkStart
and
TimerLinksZx
The logic for the linking of the timer settings can be described with a module diagram.
The figure
TimerModeZx
is selected to
Ph-Ph
and
Ph-E
.
1MRK 502 071-UEN -
Section 8
Impedance protection
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
211
Application manual
Summary of Contents for Relion REG670
Page 1: ...RELION 670 SERIES Generator protection REG670 Version 2 2 IEC Application manual...
Page 2: ......
Page 108: ...102...
Page 132: ...126...
Page 324: ...318...
Page 442: ...436...
Page 476: ...470...
Page 628: ...622...
Page 718: ...712...
Page 728: ...722...
Page 768: ...762...
Page 778: ...772...
Page 779: ...773...