normally under more stable conditions and a longer operation time delay setting is
needed, where the
tSCM
setting is used. During auto-reclosing, a shorter operation
time delay setting is preferable, where the
tSCA
setting is used. A typical value for
tSCM
can be 1 second and a typical value for
tSCA
can be 0.1 seconds.
Energizingcheck settings
AutoEnerg
and
ManEnerg
Two different settings can be used for automatic and manual closing of the circuit
breaker. The settings for each of them are:
•
Off
, the energizing function is disabled.
•
DLLB
, Dead Line Live Bus, the line voltage is below set value of
ULowLineEnerg
and the bus voltage is above set value of
UHighBusEnerg
.
•
DBLL
, Dead Bus Live Line, the bus voltage is below set value of
ULowBusEnerg
and the line voltage is above set value of
UHighLineEnerg
.
•
Both
, energizing can be done in both directions,
DLLB
or
DBLL
.
ManEnergDBDL
If the parameter is set to
On
, manual closing is also enabled when both line voltage and
bus voltage are below
ULowLineEnerg
and
ULowBusEnerg
respectively, and
ManEnerg
is set to
DLLB
,
DBLL
or
Both
.
UHighBusEnerg
and
UHighLineEnerg
The voltage level settings must be chosen in relation to the bus or line network voltage.
The threshold voltages
UHighBusEnerg
and
UHighLineEnerg
have to be set lower
than the value at which the network is considered to be energized. A typical value can
be 80% of the base voltages.
ULowBusEnerg
and
ULowLineEnerg
The threshold voltages
ULowBusEnerg
and
ULowLineEnerg
, have to be set to a value
greater than the value where the network is considered not to be energized. A typical
value can be 40% of the base voltages.
A disconnected line can have a considerable potential due to, for
instance, induction from a line running in parallel, or by being fed via
the extinguishing capacitors in the circuit breakers. This voltage can
be as high as 30% or more of the base line voltage.
Because the setting ranges of the threshold voltages
UHighBusEnerg
/
UHighLineEnerg
and
ULowBusEnerg
/
ULowLineEnerg
partly overlap each other, the
setting conditions may be such that the setting of the non-energized threshold value is
higher than that of the energized threshold value. The parameters must therefore be set
carefully to avoid overlapping.
1MRK 502 071-UEN -
Section 15
Control
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
495
Application manual
Summary of Contents for Relion REG670
Page 1: ...RELION 670 SERIES Generator protection REG670 Version 2 2 IEC Application manual...
Page 2: ......
Page 108: ...102...
Page 132: ...126...
Page 324: ...318...
Page 442: ...436...
Page 476: ...470...
Page 628: ...622...
Page 718: ...712...
Page 728: ...722...
Page 768: ...762...
Page 778: ...772...
Page 779: ...773...