Figure 217:
Typical stress magnification factor curve according ANSI/IEEE
C37.106-2003 Standard
Each turbine manufactured for different design of blades has various time restriction
limits for various frequency bands. The time limits depend on the natural frequencies
of the blades inside the turbine, corrosion and erosion of the blade edges and
additional loss of blade lifetime during the abnormal operating conditions.
The frequency limitations and their time restrictions for different types of turbines are
similar in many aspects with steam turbine limitations. Certain differences in design
and applications may result in different protective requirements. Therefore, for
different type of turbine systems, different recommendations on the time restriction
limits are specified by the manufacturer.
However, the IEEE/ANSI C37.106-2003 standard "Guide for Abnormal Frequency
Protection for Power Generating Plants" provides some examples where the time
accumulated within each frequency range is as shown in Figure
.
Section 11
1MRK 502 071-UEN -
Frequency protection
442
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
Application manual
Summary of Contents for Relion REG670
Page 1: ...RELION 670 SERIES Generator protection REG670 Version 2 2 IEC Application manual...
Page 2: ......
Page 108: ...102...
Page 132: ...126...
Page 324: ...318...
Page 442: ...436...
Page 476: ...470...
Page 628: ...622...
Page 718: ...712...
Page 728: ...722...
Page 768: ...762...
Page 778: ...772...
Page 779: ...773...